ABB SACE Emax E1.2 Operating Instructions For The Design Engineer page 80

Sace emax 2 series low voltage air circuit-breakers
Hide thumbs Also See for SACE Emax E1.2:
Table of Contents

Advertisement

Continued from the previous page
The following are the details of the protections according to standard IEC 60255-151:
Protection
Curve parameters
L
a = 0.02; b = 0.15873;
(60255-151 SI)
k = 0.16
L
a = 1; b = 0.148148;
(60255-151 VI)
k = 13.7
L
a = 2; b = 0.1;
(60255-151 EI)
k = 82
L
a = 4; b = 1;
(60255-151 I
)
k = 82
4
Table of Additional Functions of the protections
The following table summarises the additional functions combined with protections S, I, G:
ABB
ANSI
Threshold
(1)
S
If
-
startup
(Startup)
step = 0.1 In
(6)
I
I3
-
startup
(Startup)
step = 0.1 In
G
I4
-
startup
(Startup)
step = 0.02 In
(6)
S
68
-
(SdZ)
G
68
-
(SdZ)
NOTES
(1)
ANSI / IEEE C37-2 encoding.
(2)
t
calculation is valid for If values exceeding the trip threshold of the protection. Use fault current and threshold values expressed in In to calculate t
t
, as shown in the example.
t
(3)
Valid tolerances with steady-state energized trip unit or trip unit energized by auxiliary power supply, tripping time ≥ 100 ms, temperature and
currents within operating limits. If these conditions are not guaranteed, the tolerances in the table that following these notes are valid.
(4)
In the presence of auxiliary power supply, you can select all the thresholds. In self-supply mode the minimum threshold is limited to: 0.3 In (with In
= 100 A), 0.25 In (with In = 400 A) or 0.2 In (for all other sizes).
(5)
The MCR time is the time for which the protection remains active after circuit-breaker closing. Tripping time, not adjustable, as for protection I.
(6)
Startup can be activated only with the function set to fixed time.
(7)
For the startup functions, the specified time is the period during which the protection with the different threshold remains active, calculated from
the moment the startup threshold is exceeded.
(8)
With t4 = Instantaneous, the maximum tolerance is 50 ms.
Protection
Tolerance threshold
L
Activation for If in the range 1.05...1.2 I1
S
± 10 %
I
± 15 %
G
± 15 %
2I
± 15 %
Other
-
74 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
Calculation formula t
t
=
t
(t1 x k x b) / ((If / I1)
t
=
t
(t1 x k x b) / ((If / I1)
t
=
t
(t1 x k x b) / ((If / I1)
t
=
t
(t1 x k x b) / ((If / I1)
Threshold tolerance
= 0.6...10 In
± 7 % with If ≤ 6 In
± 10 % with If > 6 In
= 1.5...15 In
± 10 %
= 0.2...1 In
± 7 %
-
-
(3)
t
-1)
a
-1)
a
-1)
a
-1)
a
Time
Calculation formula t
(3)
(7)
t2
= 0.1...30 s
t
= t2
startup
step = 0.01 s
t
t3
= 0.1...30 s
≤ 30 ms
t
startup
step = 0.01 s
t
t4
= 0.1...30 s
t
= t4
startup
step = 0.01 s
t
t2
= 0.04...0.2 s
-
SdZ
step = 0.01 s
t4
= 0.04...0.2 s
-
SdZ
step = 0.01 s
Tolerance t
t
± 20 %
± 20 %
≤ 60 ms
± 20 % (60 ms with t4 = instantaneous)
≤ 60 ms
± 20 %
ABB | SACE Emax 2
Calculation example t
(3)
t
t
= 4.78 s with:
t
I1 = 0.4 In; t1 = 3 s; If = 0.8 In
t
= 6 s with:
t
I1 = 0.4 In; t1 = 3 s; If = 0.8 In
t
= 8 s with:
t
I1 = 0.4 In; t1 = 3 s; If = 0.8 In
t
= 16 s with:
t
I1 = 0.4 In; t1 = 3 s; If = 0.8 In
Tolerance t
(3)
t
The better of the two
values:
± 10 % or ± 40 ms
-
The better of the two
values:
± 10 % or ± 40 ms
-
-
Ekip Touch protection trip unit | 9 - Touch protections
(3)
t

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sace emax e2.2Sace emax e4.2Sace emax e6.2

Table of Contents