Compatibility and power supply The module can be installed combined with Ekip Dip, Touch, Hi-Touch, G Touch, and G Hi-Touch trip units,
238 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
Continued from the previous page
With the Programmable Logic function, it is possible to program the activation of the Ekip Link up to 4 bits,
each bit according to any combination of the status bits of a trip unit whose IP Address has been inserted.
These four bits are indicated as states A, B, C and D remotely programmable, and their value is transmitted
to the trip unit to which the Ekip Link module is connected.
Exclusively with Ekip Dip trip units: the module can also be used with a function similar to that of the Ekip Com
Modbus TCP module, but only with the possibility to communicate with the ABB master (e.g.: Ekip Connect,
or Ekip Control Panel).
The following table shows the ports used by the module:
Port
Service
502/tcp
Modbus TCP
18/udp
ABB proprietary
319/udp
IEEE 1588
320/udp
68/udp
DHCP Client
IMPORTANT: only one Ekip Link can be installed on each circuit-breaker.
If connected to a withdrawable version of the circuit-breaker, the module allows the connected/disconnected
position to be detected.
IMPORTANT: when the circuit-breaker is in the disconnected position, the trip unit
is disconnected from the module: in this condition, the only valid information
transmitted is:
• Connection of trip unit to Com module (Trip unit disconnected = disconnected).
• CB position (CB isolated / CB connected = CB isolated).
• Presence of com module ( = present; only valid for the module to which it is connected).
Further details are given in document
Interface for Emax 2), sections Status Global 1 [dlog], Status Accessories 1 and
Status Accessories 2.
The modules are always supplied with Ekip AUP and Ekip RTC contacts (see the chapter "16 - Other
accessories" on page 244).
and requires the presence of an Ekip Supply module in the first slot of the circuit-breaker terminal box.
Notes
When the module is used as a Modbus TCP communication module.
In case of exchange of fast information between ABB devices.
When IEEE protocol 1588 is enabled (see paragraph "Configuration",
on page 241).
DHCP Client enabled as an alternative to "Static Address = On"