Spa Bus Communication Protocol Parameters - ABB REM 610 Technical Reference Manual

Motor protection relay
Hide thumbs Also See for REM 610:
Table of Contents

Advertisement

REM 610
4.1.15.
78
Motor Protection Relay
Technical Reference Manual
Table 4.1.14.2-9 Informative event
Address Name
678
1 SPA channel
679
SPA event
Structure 4
The relay's real-time clock is stored in this structure. It can be updated by presetting
the whole register structure in one Modbus transaction.
Table 4.1.14.2-10Real-time clock structure
Address Description
721
Year
722
Month
723
Day
724
Hour
725
Minute
726
Second
727
Hundredth of a
second

SPA bus communication protocol parameters

Altering parameter values via serial communication requires the use of the SPA
password in some cases. The password is a user-defined number within the range
1...999, the default value being 1. SPA parameters are found on channels 0...5, 504
and 507.
To enter the setting mode, enter the password into parameter V160. To quit the
setting mode, enter the same password into parameter V161. The password
protection is also reactivated in case of loss of auxiliary voltage.
The HMI password can be changed via parameter V162, but it is not possible to read
the password via this parameter.
Abbreviations used in the following tables:
• R = readable data
• W = writeable data
• P = password protected writeable data
Settings
Table 4.1.15-1 Settings
Variable
Safe stall time
Weighting factor
Time constant multiplier
Prior alarm level
Restart inhibit level
Ambient temperature
Range
0...3
0...63
Range
0...99
1...12
1...31
0...23
0...59
0...59
0...99
Actual
Group/
settings (R),
Channel 1
channel 0
(R, W, P)
S1
1S1
S2
1S2
S3
1S3
S4
1S4
S5
1S5
S6
1S6
1MRS 752263-MUM
Comment
MSB = 1
Group/
Channel 2
Setting range
(R, W, P)
2S1
1)
2...120 s
2S2
20...100%
2S3
1...64
2S4
50...100%
2S5
20...80%
2S6
0...70°C