Positioning anchor plates E1.2 The following diagram shows the distance for positioning the first anchor plate for E1.2 circuit-breakers
Positioning anchor plates E2.2-
E4.2-E6.2
285 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
according to the peak current:
500/
19.69
E1.2
450/
17.72
400/
15.75
350/
13.78
300/
11.81
250/
9.84
200/
7.87
150/
5.91
100/
3.94
40
60
80
Figure 92
(1): distance of the first anchor plate from the circuit-breaker terminals
(2): peak current
The following diagram shows the distance for positioning the first anchor plate for E2.2-E4.2-E6.2 circuit-
breakers according to the peak current:
500/
19.69
E2.2
450/
17.72
400/
15.75
350/
13.78
300/
11.81
250/
9.84
200/
7.87
150/
5.91
100/
3.94
40
60
80
100
Figure 93
(1): distance of the first anchor plate from the circuit-breaker terminals
(2): peak current
100
120
140
160
E4.2
E6.2
120
140
160
180
200
220
ABB | SACE Emax 2
L
L
L
L
240
260
280
300
Ipk [kA]
(2)
Mechanical accessories | 7 - Installation
L
L
L
L