ABB SACE Emax E1.2 Operating Instructions For The Design Engineer page 202

Sace emax 2 series low voltage air circuit-breakers
Hide thumbs Also See for SACE Emax E1.2:
Table of Contents

Advertisement

196 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
Continued from the previous page
The following table shows the configuration parameters of the outputs:
Parameter
Selectable values
• None
• Prealarm L
• Delay L
• Delay S
• Opening L
• Opening S
• Opening G
• Opening I
Signal source
• Every opening
• Every delay
• Threshold1 I1
• Threshold2 I1
• CB Open
• CB Close
• Local Bus Not Active
• Custom
(2)
0.00...100.00 s
Delay
steps of 0.01 s
Contact type NO, NC
Self-latching
Off, On
Min activation
0 ms, 100 ms, 200 ms,
time
Power Controller
(1)
For the sources Threshold1 I1 and Threshold2 I1, see the chapter "9 - Touch protections", and the
paragraph "Current thresholds", on page 69.
(2)
The Custom source is a combination of default events that can be modified using the Ekip Connect software
so as to make the closing/opening of the contact correspond to a wide range of combinations of the status
bits of the trip unit.
Default
Description
The event that activates the outputs, so as to make
the contact:
None
• Closed, if set as NO.
• Open, if set as NC.
(1)
(1)
Standby time after the selected event has occurred,
and before the output is activated (if the event
0.00 s
disappears before a time equal to the delay elapsed,
the output is not activated). If 0.00 s is selected, the
value 300 μs is assigned to the parameter.
• NO = Contact normally open.
NO
• NC = Contact normally closed.
• Off = The output is deactivated when the event
disappears.
• On = When the event disappears, the output is
kept active for the minimum time selected.
Off
IMPORTANT: if the output is used for the
Power Controller function, self-latching
must not be enabled.
The "Power Controller" value can be selected only if
the output is used for the Power Controller function
(see the chapter "23 - Ekip Power Controller", on
page 131). Then the output is kept active for a fixed
time associated with the function, regardless of the
persistence of the event that activated it.
On the contrary, with self-latching enabled, the
0 ms
minimum time in which the output is kept active (once
the selected time has elapsed, the output is kept
active as long as the event that activated it persists).
IMPORTANT: if the output is not used for
the Power Controller function, the "Power
Controller" value must not be selected.
ABB | SACE Emax 2
Continued on the next page
Electronic accessories | 5 - Ekip Signalling 4K module