Access from the display With the module energized, and the Local Bus enabled, the presence of the module itself on the terminal box
189 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
activates additional menus on the display:
• To configure the synchronism function.
• To display the measurements related to the function (voltage, frequency, and phase).
• To configure the module.
• To display information on the module and synchronism status.
The presence of the module also activates a graphic summary page with the measurements of the synchronism
function and synchronism state. This page can be accessed from the Main page by touching the sides of the
display until it appears. Further information is available on page 191.
To enable the Local Bus, you need to select "On" in the menu Settings - Modules - Local Bus.
The configuration parameters of the synchronism function are different depending on whether the dead
busbar option is enabled or not.
The following table shows the path from the display to access the configuration parameters of the function,
and the parameters available with dead busbar disabled:
...
UP Protection
Advanced
Synchrocheck Protection
Signallings
...
The following table shows the path from the display to access the configuration parameters of the function,
and the parameters available with dead busbar enabled:
...
UP Protection
Advanced
Synchrocheck Protection
Signallings
...
NOTE: the module can also be configured through the Ekip Connect software (see the chapter
"16 - Other accessories", and the paragraph "Ekip Connect software" on page 245).
Activate
Dead busbar option (Off)
Ulive Threshold
Stability Time
Delta Voltage
Delta Frequency
Delta Phase
Auto Live-dead detect
Auto Deadbar detect
Primary voltage
Secondary voltage
Concatenated Ref
Contact type
Activate
Dead busbar option (On)
Udead Threshold
Ulive Threshold
Stability Time
Contact Delay
Dead bar configuration
Auto Live-dead detect
Auto Deadbar detect
Primary voltage
Secondary voltage
Concatenated Ref
Contact type
Continued on the next page