Access From The Display - ABB SACE Emax E1.2 Operating Instructions For The Design Engineer

Sace emax 2 series low voltage air circuit-breakers
Hide thumbs Also See for SACE Emax E1.2:
Table of Contents

Advertisement

Access from the display With the modules energized, and the Local Bus enabled, the presence of the modules on the terminal box
234 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
activates additional menus on the display:
• To set the modules.
• In order to display information on the modules.
To enable the Local Bus, you need to select "On" in the menu Settings - Modules - Local Bus.
The following table shows the path from the display, for setting the function and addressing of the modules:
...
Main frequency
Settings
Modules
Power Controller
...
(1)
As Ekip Com IEC 61850.
The following table shows the parameters for setting the modules. For further information, see the table on
page 235.
Selectable
Parameter
values
Force Static IP
Off, On
address
SNTP Client
Off, On
Enabled
Static IP
Displayed with static IP Address enabled, it must be selected in order to insert the IP
Address
Address of the modules.
Static Network
Displayed with static IP Address enabled, it must be selected in order to insert the subnet
Mask
mask of the modules.
Displayed with static IP Address enabled, it must be selected in the presence of
Static
multiple subnets, in order to insert the IP Address of the node to which the modules are
Gateway addr
connected.
SNTP Server
Displayed with SNTP client enabled. "On" has to be selected to insert the IP address of
Address
the server with whose SNTP clock signal the modules are to be synchronised.
The following table shows the path from the display for accessing information on the modules:
Protection Unit
Circuit-breaker
About
Modules
Power Controller
Local/Remote
Local Bus
...
Ekip Com IEC 61850
Ekip Com IEC 61850 *R
...
Functions
Default
Description
• Off = Dynamic IP address.
Off
• On = Static IP address.
• Off = Synchronism with the SNTP clock signal
Off
disabled.
• On = Synchronism with the SNTP clock signal enabled.
Electronic accessories | 13 - Ekip Com IEC 61850 modules
ABB | SACE Emax 2
Force Static IP address
SNTP Client Enabled
Static IP Address
Static Network Mask
Static Gateway addr
SNTP Server Address
(1)
...
Ekip Com IEC 61850
Ekip Com IEC 61850 *R
...
Continued on the next page