5.3.3.2
Type
Input (numera-
I1
%
tor)
-
-
I2
I3
-
-
b
Master Reset
I4
Description:
The input value at I1 is divided by the parameter value P1.
1 I
O1
O
2
=
−
=
1 P
The result of the division is limited to ±P2 (max. to ±327.67%).
As long as status TRUE is present at I4 (Master Reset), the output value O1 is 0.
Example:
I1=14000 (=140.00%)
P1=4000 (=40.00%)
Note:
Percentages [%] have two decimals.
For example: Value 12345
If P1 is set to value 0, the output has the value 327.67%. The sign is applied from the input
value.
5.3.3.3
Type
Input (denomina-
%
I1
tor)
I2
-
-
-
-
I3
b
Master Reset
I4
Description:
The parameter value P1 is divided by the input value at I1 (reciprocal).
1 P
O1
O
2
=
−
=
1 I
The result of the division is limited to ±P2 (max. to ±327.67%).
As long as status TRUE is present at I4 (Master Reset), the output value O1 is 0.
Example:
I1=14000 (=140.00%)
P1=4000 (=40.00%)
Note:
Percentages [%] have two decimals.
For example: Value 12345
If I1 has value 0, output O1 has value 327.67% or the value of P2.
08/10
08/10
[337] Division by constant
Function
Type
O1
%
%
O2
P1
%
%
P2
O1
= 140.00% / 40.00%
= (1.4000 / 0.4000)
= |350.00%| limit
= 327.67%
= 123.45% = 1.2345
IN
[338] Division P1 by I1, reciprocal
Function
O1
O2
P1
P2
O1
= 40.00% / 140.00%
= (0.4000 / 1.4000)
= 28.57%
= 123.45% = 1.2345
IN
Function
I1
O1 =
P1
inverted output = -1
Constant (denominator)
upper and lower limit
Type
Function
P1
%
O1 =
I1
%
inverted output = -1
%
Constant (numerator)
%
upper and lower limit
VPLC / PLC
VPLC / PLC
95
95
Need help?
Do you have a question about the AGILE and is the answer not in the manual?
Questions and answers