Warning Messages

Important Note: Warning Message Status must be enabled before any warnings in this
menu can be displayed.
Usage:
These messages serve as a flag to service a scanner or as an early warning
that potential problems could arise. They are particularly useful in factories
that run constantly and can't afford down time.
Definition:
Warning messages that relate to the environment and condition of the scanner
can be defined and set to activate specific outputs.
Note: When enabled, the error condition will override all other operational
modes configured for the output.When enabled, laser current and
NOVRAM warning messages will be transmitted to the host or any active
port whenever the pre-defined conditions are met.
Function:
When enabled, warning messages will be transmitted to the host or any
active port.
Note: This option must be enabled before any other warning messages can
be transmitted.
Warning Message Status
<K400,warning message
Serial Cmd:
NOVRAM/reset warning status>
Disabled
Default:
Options:
0 = Disabled
1 = Enabled
Laser High Status
When enabled, a message is transmitted whenever the laser current exceeds a factory-calibrated
reference value which cannot be altered. The message repeats once every 30 minutes
until the condition is corrected.
Usage:
Alerts the user to impending laser failure.
Definition:
Enables the Laser High message.
Serial Cmd:
<K400,warning message
NOVRAM/reset warning status>
Enabled
Default:
Options:
0 = Disabled
MS-890 Industrial Automation Scanner User Manual
status,laser high status,laser low status,
status,laser high
status,laser low status,
1 = Enabled