Cabinet design and EMC Booksize
12.7 Connection systems
12.7.3
Current-carrying capacity and derating factors for power cables and signal
cables
The current carrying capacity of PVC/PUR-insulated copper cables is specified for routing
types B1, B2 and C under continuous operating conditions in the table below with reference
to an ambient air temperature of 40° C. For other ambient temperatures, the values must be
corrected by the factors listed in the "Derating factors for deviating ambient temperatures"
table.
Table 12- 17 Routing types
B1
B2
C
Table 12- 18 Current carrying capacity according to EN 60204-1 for 40° C ambient temperature
Cross-section
mm
Signal cables
0.20
0.50
0.75
Power cables
0.75
1.00
1.50
2.50
4
6
10
16
25
35
50
70
95
120
714
Cables in conduits or cable ducts
Multi-conductor cables in conduits or cable ducts
Cables along walls, without conduits or cable ducts
2
Current carrying capacity, effective; AC 50/60 Hz or DC
For routing type
B1
B2
A
A
4.3
7.5
9
8.6
8.5
10.3
10.1
13.5
13.1
18.3
17.4
24
23
31
30
44
40
59
54
77
70
96
86
117
103
149
130
180
165
208
179
C
A
4.4
7.5
9.5
9.8
11.7
15.2
21
28
36
50
66
84
104
125
160
194
225
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8