Connecting The Motor Cable - Siemens SINAMICS S120 Manual

Power units in booksize c/d-type format
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Note
Cables for UL applications
For UL applications, only 60/75 °C copper cables may be used.
4.1.4

Connecting the motor cable

Connecting conductors to the push-in connector
The state of the push-in plug connector when it is
delivered:
The 6 locking levers are locked in the engaged
state, the terminals open.
Lock the terminals by pressing a 0.8 x 4 mm slot-
head screwdriver down vertically on the locking
lever. Make sure that the conductor has been
inserted as far as it will go. Start with W2, V2, U2,
and by gently pulling on the conductors ensure
that they are securely engaged in the terminals
before you continue with the protective conductor
and the brake conductors in the same way.
Power Units in Booksize C/D-Type Format
Manual, 12/2018, 6SL3097-5AC20-0BP0
Motor connection, shield support and fabrication
4.1 Motor plug connector for Motor Modules 3 A ... 30 A
Insert the conductors into the open terminals. For
cross-sections from 4 mm² and higher it is helpful
if U2, V2, W2 are simultaneously inserted.
Assembled push-in connector
79