2.2 CONFIGURATION SETTINGS
112: PREFLT – PREFAULT CYCLES
PREFLT selects the number of pre-trigger (or pre-fault) cycles in each oscillography data set. It can be set from
1 to 20. Setting 111: NUM FLTS determines the total number of cycles per storage event, as explained above,
and PREFLT determines how many of these are pre-trigger cycles.
113: OSC TRIG – EXTERNAL OSCILLOGRAPHY TRIGGER
2
A DGP system trip always causes oscillography to be stored. OSC TRIG enables or disables an additional
oscillography trigger by an external digital input (DI5). Refer to Section 1.4.9: FAULT REPORT & OSCILLOG-
RAPHY DATA on page 1–21 for further explanation. OSC TRIG may be set to 0 (DI ENA) or 1 (DI DIS).
114: NOM VOLT – NOMINAL VOLTAGE
NOM VOLT can be set from 100.0 to 140.0 V (phase-to-phase).
For the sample generator system,
115: RATEDCUR – RATED CURRENT
RATEDCUR can be set from 0.10 to 9.99 A (0.02 to 1.99 A for models with 1 A rating).
For the sample generator system,
116: VT CONN – VOLTAGE TRANSFORMER CONNECTION
VT CONN may be set to 0 (WYE) or 1 (DELTA). VT CONN must be set to identify the VT connections that sup-
ply AC voltage to the DGP.
117: NCTRATIO – NEUTRAL CURRENT TRANSFORMER RATIO
NCTRATIO setting is available in all DGP models except DGP***AAA. It can be set from 1 to 50000. This set-
ting applies to I
current only; refer to Current Transformer Ratio (Setting 106: CT RATIO) for the CT ratio set-
NR
ting of other current inputs.
For the sample generator system,
Example Settings (based on Figure 2–1: SAMPLE GENERATOR SYSTEM):
UNITID =1
SYSFREQ = 60
SEL TVM = as required
SEL TCM = as required
SELPRIM = PRIMARY (0)
CT RATIO = 1600
VT RATIO = 157.5
COMMPORT = 2401
2-
12
18000
NOM VOLT
=
---------------------------------- -
(
18900 120
211765
RATEDCUR
=
--------------------------------------------------------- -
(
×
1.732
18
8000
NCTRATIO
=
------------ -
PHASE = A-B-C (0)
TIMESYNC = INTRNL (0)
NUM FLTS = 3
NOM VOLT = 114.3 volts
RATEDCUR = 4.25 amps
VT CONN = WYE (0)
NCTRATIO = 1600
DGP Digital Generator Protection System
2 CALCULATION OF SETTINGS
=
114.3 V
)
4.25 A
=
) 8000 5 ⁄
(
)
=
1600
5

2.2.2 EXAMPLE CONFIGURATION SETTINGS