Faults and Alarms
List of Faults and Alarms
F30809
Power unit: Switching information not valid
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
For 3P gating unit:
The last switching status word in the setpoint telegram is identified by the end ID. Such an end ID was not found.
Remedy:
- carry out a POWER ON (power off/on) for all components.
- upgrade firmware to later version.
- contact the Hotline.
A30810 (F)
Power unit: Watchdog timer
Reaction:
NONE
Acknowledge:
NONE
Cause:
When booting it was detected that the cause of the previous reset was an SAC watchdog timer overflow.
Remedy:
- carry out a POWER ON (power off/on) for all components.
- upgrade firmware to later version.
- contact the Hotline.
F30850
Power unit: Internal software error
Reaction:
OFF1 (NONE, OFF2, OFF3)
Acknowledge:
POWER ON
Cause:
An internal software error has occurred in the power unit.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- replace power unit.
- if required, upgrade the firmware in the power unit.
- contact the Hotline.
F30899 (N, A)
Power unit: Unknown fault
Reaction:
NONE (IASC/DCBRAKE, OFF1, OFF2, OFF3, STOP2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
A fault occurred on the power unit that cannot be interpreted by the Control Unit firmware.
This can occur if the firmware on this component is more recent than the firmware on the Control Unit.
Fault value (r0949, interpret decimal):
Fault number.
Note:
If required, the significance of this new fault can be read about in a more recent description of the Control Unit.
Remedy:
- replace the firmware on the power unit by an older firmware version (r0128).
- upgrade the firmware on the Control Unit (r0018).
F30903
Power unit: I2C bus error occurred
Reaction:
OFF2 (IASC/DCBRAKE, NONE, OFF1, OFF3, STOP2)
Acknowledge:
IMMEDIATELY
Cause:
Communications error with an EEPROM or A/D converter.
Fault value (r0949, interpret hexadecimal):
80000000 hex:
- internal software error.
00000001 hex ... 0000FFFF hex:
- module fault.
Remedy:
Re fault value = 80000000 hex:
- upgrade firmware to later version.
Re fault value = 00000001 hex ... 0000FFFF hex:
- replace the module.
3-648
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
© Siemens AG 2009 All Rights Reserved