Siemens CU230P-2 HVAC Parameter Manual page 489

Sinamics g120 control units
Hide thumbs Also See for CU230P-2 HVAC:
Table of Contents

Advertisement

n_set_fixed Bit 0 p1020 [C]
(722.3)
n_set_fixed Bit 1 p1021 [C]
(722.4)
n_set_fixed Bit 2 p1022 [C]
(722.5)
n_set_fixed Bit 3 p1023 [C]
Inhib neg dir p1110 [C]
Inhib pos dir p1111 [C]
Setp inv p1113 [C]
(722.1)
Mop raise p1035 [C]
Mop lower p1036 [C]
Bypass RFG p1122 [C]
1
2
Internal control/status words
Control word, setpoint channel
Bit No.
Control word, setpoint channel (r1198)
1 = Fixed setpoint, bit 0
0
1
1 = Fixed setpoint, bit 1
2
1 = Fixed setpoint, bit 2
3
1 = Fixed setpoint, bit 3
(0)
4
Reserved
(0)
5
1 = Inhibit negative direction of rotation
(0)
6
1 = Inhibit positive direction of rotation
7
Reserved
8
Reserved
9
Reserved
Reserved
10
11
1 = Dir of rot reversal
12
Reserved
(0)
13
1 = Motorized potentiometer, raise
(0)
14
1 = Motorized potentiometer, lower
15
1 = Bypass ramp-function generator
(0)
3
4
STW setpoint chan
r1198
r1198
To fixed speed setpoints [3010.2]
r1198.0
r1198.1
To fixed speed setpoints [3010.2]
r1198.2
To fixed speed setpoints [3010.2]
r1198.3
To fixed speed setpoints [3010.2]
To direction of rotation limiting and
r1198.5
direction of rotation reversal [3040.3]
To direction of rotation limiting and
r1198.6
direction of rotation reversal [3040.5]
To direction of rotation limiting and
r1198.11
direction of rotation reversal [3040.2]
r1198.13
To the motorized potentiometer [3020.1]
To the motorized potentiometer [3020.1]
r1198.14
r1198.15
To the setpoint channel [3060.1] [3070.3]
5
6
Function diagram
FP_2505_97_51.vsd
G120 CU230P-2
29.10.2009
V4.3
7
8
- 2505 -

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu230p-2 dpCu230p-2 can