n_act = smoothed speed actual value r2169 [8010.2].
<1>
1
2
Internal control/status words
Status word, monitoring functions 1
Bit No.
Status word, monitoring functions 1 (r2197)
[8020.8]
0
1 = |n_act| <= n_min p1080
[8010.8]
1
1 = |n_act| <= speed threshold value 2 (p2155)
1
2
1 = |n_act| > speed threshold value 2 (p2155)
[8011.8]
3
1 = n_act >= 0
[8020.8]
4
1 = |n_act| >= n_set
[8020.8]
1 = |n_act| <= n_standstill p1226
5
[8010.8]
6
1 = |n_act| > n_max
[8011.8]
7
1 = Speed setpoint - actual value deviation within tolerance t_off
[8020.8]
8
1 = I_act >= I_threshold p2170
[8020.8]
9
1 = Vdc_act <= Vdc_threshold p2172
[8020.8]
10
1 = Vdc_act > Vdc_threshold p2172
[8020.8]
11
1 = Load missing
12
1 = |n_act| > n_max (with delay)
[8021.8]
13
Reserved
14
Reserved
15
Reserved
3
4
r2197.0
<1>
r2197.1
<1>
r2197.2
r2197.3
r2197.4
r2197.5
r2197.6
r2197.7
r2197.8
r2197.9
r2197.10
r2197.11
r2197.12
5
6
Function diagram
FP_2534_97_51.vsd
G120 CU230P-2
29.10.2009
V4.3
ZSW monitor 1
r2197
r2197
7
8
- 2534 -