Siemens CU230P-2 HVAC Parameter Manual page 151

Sinamics g120 control units
Hide thumbs Also See for CU230P-2 HVAC:
Table of Contents

Advertisement

p1203[0...n]
Flying restart search rate factor / FlyRst v_Srch Fact
PM240
Access level: 3
PM250, PM260
Can be changed: U, T
Min
10 [%]
Description:
The value influences the rate at which the output frequency is changed during a flying restart . A higher value
results in a longer search time.
Caution:
An unfavorable parameter value can result in the motor behaving in an uncontrollable fashion.
For vector control, a value that is too low or too high can cause flying restart to become unstable.
Note:
The parameter factory setting is selected so that standard induction motors that are rotating can be found and
restarted as quickly as possible (fast flying restart).
With this presetting, if the motor is not found (e.g. for motors that are accelerated as a result of active loads) we rec-
ommend that the search rate is reduced (by increasing p1203).
r1204.0...13
CO/BO: Flying restart, V/f control status / FlyRest Vf st
Access level: 4
Unit: -
Description:
Displays the status for checking and monitoring flying restart states in the V/f control mode.
Bit field:
Bit
Signal name
00
Current impressed
01
No current flow
02
Voltage input
03
Voltage reduced
04
Start ramp-function generator
05
Wait for execution
06
Slope filter act
07
Positive gradient
08
Current < thresh
09
Current minimum
10
Search in the positive direction
11
Stop after positive direction
12
Stop after negative direction
13
No result
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Calculated: -
Scaling: -
Max
4000 [%]
Calculated: -
Scaling: -
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Parameters
List of Parameters
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
100 [%]
Data type: Unsigned16
Data set: -
0 signal
No
No
No
No
No
No
No
No
No
No
No
No
No
No
FP
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1-151

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu230p-2 dpCu230p-2 can

Table of Contents