Siemens CU230P-2 HVAC Parameter Manual page 642

Sinamics g120 control units
Hide thumbs Also See for CU230P-2 HVAC:
Table of Contents

Advertisement

Faults and Alarms
List of Faults and Alarms
A30034
Power unit: Internal overtemperature
Reaction:
NONE
Acknowledge:
NONE
Cause:
The alarm threshold for internal overtemperature has been reached.
If the temperature inside the unit continues to increase, fault F30036 may be triggered.
- ambient temperature might be too high.
- insufficient cooling, fan failure.
Fault value (r0949, interpret binary):
Bit 0 = 1: Control electronics range.
Bit 1 = 1: Power electronics range.
Remedy:
- check the ambient temperature.
- check the fan for the inside of the unit.
F30035
Power unit: Air intake overtemperature
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
The air intake in the power unit has exceeded the permissible temperature limit.
For air-cooled power units, the temperature limit is at 55 °C.
- ambient temperature too high.
- insufficient cooling, fan failure.
Fault value (r0949, interpret decimal):
Temperature [1 bit = 0.01 °C].
Remedy:
- check whether the fan is running.
- check the fan elements.
- check whether the ambient temperature is in the permissible range.
Notice:
This fault can only be acknowledged after this alarm threshold for alarm A05002 has been undershot.
F30036
Power unit: Internal overtemperature
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
For chassis power units, the following applies:
The temperature inside the drive converter has exceeded the permissible temperature limit.
- insufficient cooling, fan failure.
- overload.
- ambient temperature too high.
Fault value (r0949, interpret binary):
Bit 0 = 1: Control electronics range.
Bit 1 = 1: Power electronics range.
Remedy:
- check whether the fan is running.
- check the fan elements.
- check whether the ambient temperature is in the permissible range.
Notice:
This fault can only be acknowledged once the permissible temperature limit minus 5 K has been undershot.
3-642
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009