Parameters
List of Parameters
p1456[0...n]
Speed controller P gain adaptation lower starting point / n_ctrl AdaptKpLow
Access level: 4
Can be changed: U, T
Min
0.00 [%]
Description:
Sets the lower starting point of the adaptation range for the additional adaptation of the P gain of the speed control-
ler.
The values are in % and refer to the set source of the adaptation signal.
Dependency:
Refer to: p1455, p1457, p1458, p1459
Note:
If the upper transition point p1457 of the speed controller adaptation is set to lower values than the lower transition
p1456, then the controller gain below p1457 is adapted with p1459 and above p1456, with p1458.
p1457[0...n]
Speed controller P gain adaptation upper starting point / n_ctrl AdaptKp up
Access level: 4
Can be changed: U, T
Min
0.00 [%]
Description:
Sets the upper starting point of the adaptation range for the additional adaptation of the P gain of the speed control-
ler.
The values are in % and refer to the set source of the adaptation signal.
Dependency:
Refer to: p1455, p1456, p1458, p1459
Note:
If the upper transition point p1457 of the speed controller adaptation is set to lower values than the lower transition
p1456, then the controller gain below p1457 is adapted with p1459 and above p1456, with p1458.
p1458[0...n]
Adaptation factor, lower / Adapt_factor lower
Access level: 4
Can be changed: U, T
Min
0.0 [%]
Description:
Sets the adaptation factor before the adaptation range (0 % ... p1456) to additionally adapt the P gain of the
speed/velocity controller.
Dependency:
Refer to: p1455, p1456, p1457, p1459
Note:
If the upper transition point p1457 of the speed controller adaptation is set to lower values than the lower transition
p1456, then the controller gain below p1457 is adapted with p1459 and above p1456, with p1458.
p1459[0...n]
Adaptation factor, upper / Adapt_factor upper
Access level: 4
Can be changed: U, T
Min
0.0 [%]
Description:
Sets the adaptation factor after the adaptation range (> p1457) to additionally adapt the P gain of the speed/velocity
controller.
Dependency:
Refer to: p1455, p1456, p1457, p1458
Note:
If the upper transition point p1457 of the speed controller adaptation is set to lower values than the lower transition
p1456, then the controller gain below p1457 is adapted with p1459 and above p1456, with p1458.
1-182
Calculated: -
Scaling: -
Max
400.00 [%]
Calculated: -
Scaling: -
Max
400.00 [%]
Calculated: -
Scaling: -
Max
200000.0 [%]
Calculated: -
Scaling: -
Max
200000.0 [%]
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0.00 [%]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0.00 [%]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
100.0 [%]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
100.0 [%]