Parameters
List of Parameters
r2019[0...7]
Comm int error statistics / Comm err
Access level: 4
Unit: -
Description:
Displays the receive errors at the commissioning interface (USS, RS232).
Index:
[0] = Number of error-free telegrams
[1] = Number of rejected telegrams
[2] = Number of framing errors
[3] = Number of overrun errors
[4] = Number of parity errors
[5] = Number of starting character errors
[6] = Number of checksum errors
[7] = Number of length errors
p2020
Field bus interface baud rate / Field bus baud
CU230P-2 HVAC
Access level: 2
Can be changed: T
Min
4
Description:
Sets the baud rate for the field bus interface (RS485).
Value:
4:
5:
6:
7:
8:
9:
10:
11:
12:
13:
Notice:
For p0014 = 1, the following applies:
After the value has been modified, no further parameter modifications can be made and the status is shown in
r3996. Modifications can be made again when r3996 = 0.
Note:
Field bus interface.
Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
When p2030 = 1 (USS), the following applies:
Min./max./factory setting: 4/13/8
When p2030 = 2 (MODBUS), the following applies:
Min./max./factory setting: 5/7/7
If p2030 = 5 (BACnet), the following applies:
Possible values/factory setting: (6, 7, 8, 10) / 6
1-228
2400 Baud
4800 Baud
9600 Baud
19200 Baud
38400 Baud
57600 Baud
76800 Baud
93750 Baud
115200 Baud
187500 Baud
Calculated: -
Scaling: -
Calculated: -
Scaling: -
Max
13
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Data type: Unsigned32
Data set: -
Data type: Integer16
Data set: -
Factory setting
8
© Siemens AG 2009 All Rights Reserved