Parameters
List of Parameters
p2042
PROFIBUS Ident Number / PB Ident No.
CU230P-2 DP
Access level: 3
Can be changed: T
Min
0
Description:
Sets the PROFIBUS Ident Number (PNO-ID).
SINAMICS can be operated with various identities on PROFIBUS. This allows the use of a PROFIBUS GSD that is
independent of the device (e.g. PROFIdrive VIK-NAMUR with Ident Number 3AA0 hex).
Value:
0:
1:
Notice:
For p0014 = 1, the following applies:
After the value has been modified, no further parameter modifications can be made and the status is shown in
r3996. Modifications can be made again when r3996 = 0.
Note:
Every change only becomes effective after a POWER ON.
r2043.0...2
BO: PROFIdrive PZD state / PD PZD state
CU230P-2 DP
Access level: 3
Unit: -
Description:
Displays the PROFIdrive PZD state.
Bit field:
Bit
Signal name
00
Setpoint failure
02
Fieldbus running
Dependency:
Refer to: p2044
Note:
When using the "setpoint failure" signal, the bus can be monitored and an application-specific response triggered
when the setpoint fails.
p2044
PROFIdrive fault delay / PD fault delay
CU230P-2 DP
Access level: 3
Can be changed: U, T
Min
0 [s]
Description:
Sets the delay time to initiate fault F01910 after a setpoint failure.
The time until the fault is initiated can be used by the application. This means that is is possible to respond to the
failure while the drive is still operational (e.g. emergency retraction).
Dependency:
Refer to: r2043
Refer to: F01910
p2047
PROFIBUS additional monitoring time / PB suppl t_monit
CU230P-2 DP
Access level: 3
Can be changed: U, T
Min
0 [ms]
Description:
Sets the additional monitoring time to monitor the process data received via PROFIBUS.
The additional monitoring time enables short bus faults to be compensated.
If no process data is received within this time, an appropriate message is output.
Dependency:
Refer to: F01910
1-234
SINAMICS S/G
VIK-NAMUR
Calculated: -
Scaling: -
Max
1
Calculated: -
Scaling: -
1 signal
Yes
Yes
Calculated: -
Scaling: -
Max
100 [s]
Calculated: -
Scaling: -
Max
20000 [ms]
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Data type: Integer16
Data set: -
Factory setting
0
Data type: Unsigned8
Data set: -
0 signal
No
No
Data type: FloatingPoint32
Data set: -
Factory setting
0 [s]
Data type: FloatingPoint32
Data set: -
Factory setting
0 [ms]