r2399.0...8
CO/BO: Hibernation status word / Hib ZSW
Access level: 3
Unit: -
Description:
Displays the status word for the "Hibernation" function.
Bit field:
Bit
Signal name
00
Hibernation enabled (p2398 <> 0)
01
Hibernation active
02
Hibernation delay time active
03
Hibernation boost active
04
Hibernation motor powered down
05
Hibernation motor powered down cyclic
restart active
06
Hibernation motor restarts
07
Hibernation supplies total setpoint for ramp-
function generator
08
Hibernation bypasses ramp-fct generator in
setpoint channel
Dependency:
Refer to: p2398
Refer to: A07325
p2900[0...n]
CO: Fixed value 1 [%] / Fixed value 1 [%]
Access level: 3
Can be changed: U, T
Min
-10000.00 [%]
Description:
Sets a fixed percentage.
Dependency:
Refer to: p2901, p2930
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note:
The value can be used to interconnect a scaling function (e.g. scaling of the main setpoint)
p2901[0...n]
CO: Fixed value 2 [%] / Fixed value 2 [%]
Access level: 3
Can be changed: U, T
Min
-10000.00 [%]
Description:
Sets a fixed percentage.
Dependency:
Refer to: p2900, p2930
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note:
The value can be used to interconnect a scaling function (e.g. scaling of the supplementary setpoint)
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Calculated: -
Scaling: -
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Scaling: PERCENT
Max
10000.00 [%]
Calculated: -
Scaling: PERCENT
Max
10000.00 [%]
Parameters
List of Parameters
Data type: Unsigned32
Data set: -
0 signal
No
No
No
No
No
No
No
No
No
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0.00 [%]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0.00 [%]
FP
-
-
-
-
-
-
-
-
-
1-291