Siemens CU230P-2 HVAC Parameter Manual page 218

Sinamics g120 control units
Hide thumbs Also See for CU230P-2 HVAC:
Table of Contents

Advertisement

Parameters
List of Parameters
p1910
Motor data identification selection / MotID selection
Access level: 3
Can be changed: T
Min
0
Description:
Sets the motor data identification routine.
The motor data identification routine is carried out after the next power-on command.
p1910 = 1:
All motor data and the drive converter characteristics are identified and then transferred to the following parame-
ters:
p0350, p0354, p0356, p0357, p0358, p0360, p1825, p1828, p1829, p1830
After this, the control parameter p0340 = 3 is automatically calculated.
p1910 = 20:
Only for internal SIEMENS use.
Value:
0:
1:
2:
20:
21:
22:
23:
24:
25:
Dependency:
"Quick commissioning" must be carried out (p0010 = 1, p3900 > 0) before executing the motor data identification
routine!
When selecting the motor data identification routine, the drive data set changeover is suppressed.
Refer to: p1900
Caution:
After the motor data identification (p1910 > 0) has been selected, alarm A07991 is output and a motor data identifi-
cation routine is carried out as follows at the next power-on command:
- current flows through the motor and a voltage is present at the drive converter output terminals.
- during the identification routine, the motor shaft can rotate through a maximum of half a revolution.
- however, no torque torque is generated.
Notice:
To permanently accept the determined settings they must be saved in a non-volatile fashion (p0971).
Note:
When setting p1910, the following should be observed:
1. "With acceptance" means:
The parameters specified in the description are overwritten with the identified values and therefore have an influ-
ence on the controller setting.
2. "Without acceptance" means:
The identified parameters are only displayed in the range r1912 ... r1926 (service parameters). The controller set-
tings remain unchanged.
p1911
Number of phases to be identified / Qty ph to ident
Access level: 4
Can be changed: T
Min
1
Description:
Sets the number of phases to be identified.
Value:
1:
2:
3:
Note:
When identifying with several phases, the accuracy increases and also the time it takes to make the measurement.
1-218
Inhibited
Complete identification (ID) and acceptance of motor data
Complete identification (ID) of motor data without acceptance
Voltage vector input
Voltage vector input without filter
Rectangular voltage vector input without filter
Triangular voltage vector input without filter
Rectangular voltage vector input with filter
Triangular voltage vector input with filter
1 phase U
2 phases U, V
3 phases U, V, W
Calculated: -
Scaling: -
Max
25
Calculated: -
Scaling: -
Max
3
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Data type: Integer16
Data set: -
Factory setting
0
Data type: Integer16
Data set: -
Factory setting
1
© Siemens AG 2009 All Rights Reserved