Siemens CU230P-2 HVAC Parameter Manual page 106

Sinamics g120 control units
Hide thumbs Also See for CU230P-2 HVAC:
Table of Contents

Advertisement

Parameters
List of Parameters
p0806
BI: Inhibit master control / PcCtrl inhibit
Access level: 3
Can be changed: T
Min
-
Description:
Sets the signal source to block the master control.
Dependency:
Refer to: r0807
Note:
The commissioning software (drive control panel) uses the master control.
r0807.0
BO: Master control active / PcCtrl active
Access level: 3
Unit: -
Description:
Displays what has the master control.
The drive can be controlled via the BICO interconnection or from external (e.g. the commissioning software).
Bit field:
Bit
Signal name
00
Master control active
Dependency:
Refer to: p0806
Notice:
The master control only influences control word 1 and speed setpoint 1. Other control words/setpoints can be trans-
ferred from another automation device.
Note:
Bit 0 = 0: BICO interconnection active
Bit 0 = 1: Master control for PC/AOP
The master control is used from the commissioning software (drive control panel) and from the Advanced Operator
Panel (AOP, LOCAL mode).
p0809[0...2]
Copy Command Data Set CDS / Copy CDS
Access level: 2
Can be changed: T
Min
0
Description:
Copies one Command Data Set (CDS) into another.
Index:
[0] = Source Command Data Set
[1] = Target Command Data Set
[2] = Start copying procedure
Note:
Procedure:
1. In Index 0, enter which command data set should be copied.
2. In Index 1, enter the command data set that is to be copied into.
3. Start copying: Set index 2 from 0 to 1.
p0809[2] is automatically set to 0 when copying is completed.
p0810
BI: Command Data Set selection CDS bit 0 / CDS select., bit 0
Access level: 2
Can be changed: T
Min
-
Description:
Sets the signal source to select the Command Data Set bit 0 (CDS bit 0).
Dependency:
Refer to: r0050, p0811, r0836
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
The Command Data Set selected using the binector inputs is displayed in r0836.
The currently effective command data set is displayed in r0050.
A Command Data Set can be copied using p0809.
1-106
Calculated: -
Scaling: -
Max
-
Calculated: -
Scaling: -
1 signal
Yes
Calculated: -
Scaling: -
Max
3
Calculated: -
Scaling: -
Max
-
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Data type: U32 / Binary
Data set: -
Factory setting
0
Data type: Unsigned8
Data set: -
0 signal
No
Data type: Unsigned8
Data set: -
Factory setting
0
Data type: U32 / Binary
Data set: -
Factory setting
0
© Siemens AG 2009 All Rights Reserved
FP
5030,
6031