Siemens CU230P-2 HVAC Parameter Manual page 162

Sinamics g120 control units
Hide thumbs Also See for CU230P-2 HVAC:
Table of Contents

Advertisement

Parameters
List of Parameters
p1251[0...n]
Vdc controller integral time / Vdc_ctrl Tn
PM230
Access level: 3
PM240
Can be changed: U, T
Min
0 [ms]
Description:
Sets the integral time for the DC-link voltage controller (Vdc_min controller, Vdc_max controller).
Dependency:
The effective integral time is obtained taking into account p1243 (Vdc_max controller dynamic factor).
Note:
p1251 = 0 deactivates the integral component of the Vdc controller.
p1252[0...n]
Vdc controller rate time / Vdc_ctrl t_rate
PM230
Access level: 3
PM240
Can be changed: U, T
Min
0 [ms]
Description:
Sets the rate time constant for the DC-link voltage controller (Vdc_min controller, Vdc_max controller).
Dependency:
The effective rate time is obtained taking into account p1243 (Vdc_max controller dynamic factor).
p1254
Vdc_max controller automatic ON level detection / Vdc_max SenseOnLev
PM230
Access level: 3
Can be changed: U, T
Min
0
Description:
Activates/deactivates the automatic sensing of the switch-in level for the Vdc_max controller.
Value:
0:
1:
p1254
Vdc_max controller automatic ON level detection / Vdc_max SenseOnLev
PM240
Access level: 3
Can be changed: U, T
Min
0
Description:
Activates/deactivates the automatic sensing of the switch-in level for the Vdc_max controller.
Value:
0:
1:
p1255[0...n]
Vdc_min controller time threshold / Vdc_min t_thresh
PM240
Access level: 3
Can be changed: U, T
Min
0.000 [s]
Description:
Sets the time threshold for the Vdc_min controller (kinetic buffering). If this value is exceeded a fault is output; the
required response can be parameterized.
Prerequisite: p1256 = 1.
Dependency:
Refer to: F07406
Notice:
If a time threshold has been parameterized, the Vdc_max controller should also be activated (p1240 = 3) so that the
drive does not shut down with overvoltage when Vdc_min control is exited (due to the time violation) and in the
event of fault response OFF3. It is also possible to increase the OFF3 ramp-down time p1135.
1-162
Automatic detection inhibited
Automatic detection enabled
Automatic detection inhibited
Automatic detection enabled
Calculated: -
Scaling: -
Max
10000 [ms]
Calculated: -
Scaling: -
Max
1000 [ms]
Calculated: -
Scaling: -
Max
1
Calculated: -
Scaling: -
Max
1
Calculated: -
Scaling: -
Max
1800.000 [s]
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0 [ms]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0 [ms]
Data type: Integer16
Data set: -
Factory setting
0
Data type: Integer16
Data set: -
Factory setting
1
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0.000 [s]
© Siemens AG 2009 All Rights Reserved