p2024[0...2]
Fieldbus interface times / Fieldbus times
CU230P-2 HVAC
Access level: 3
Can be changed: U, T
Min
0 [ms]
Description:
Sets the time values for the fieldbus interface.
The following applies for MODBUS:
p2024[0]: Maximum permissible telegram processing time of the MODBUS slave in which a reply is sent back to the
MODBUS master.
p2024[1]: Character delay time (time between individual characters in the telegram).
p2024[2]: Telegram pause time (pause time between two telegrams).
The following applies for BACnet:
p2024[0]: APDU timeout.
p2024[1,2]: Not relevant.
Index:
[0] = Max. processing time
[1] = Character delay time
[2] = Telegram pause time
Dependency:
Refer to: p2020, p2030
Note:
Re p2024[1,2] (MODBUS):
If the field bus baud rate is changed (p2020), the default time settings are restored.
The default setting is the time required for 1.5 characters (p2024[1]) or 3.5 characters (p2024[2]) (depending on the
set baud rate).
p2025[0...3]
Fieldbus interface BACnet settings / BACnet setting
CU230P-2 HVAC
Access level: 3
Can be changed: U, T
Min
0
Description:
Sets the communication parameters for BACnet.
p2025[0]:
Device object instance number (0 ... 4194303).
p2025[1]:
Maximum number of info frames (1 ... 10).
p2025[2]:
Number of APDU retries (0 ... 39).
p2025[3]:
Maximum master address (1 ... 127).
Index:
[0] = Device object instance number
[1] = Maximum number of info frames
[2] = Number of APDU retries
[3] = Maximum master address
Dependency:
Refer to: p2030
p2026[0...3]
Fieldbus interface BACnet COV increment / BACnet COV incr
CU230P-2 HVAC
Access level: 3
Can be changed: U, T
Min
0.000
Description:
Sets BACnet COV (change of value) increment values.
Index:
[0] = Analog input 0
[1] = Analog input 1
[2] = Analog input 2
[3] = Analog input 3
Dependency:
Refer to: p2030
1-230
Calculated: -
Scaling: -
Max
10000 [ms]
Calculated: -
Scaling: -
Max
4194303
Calculated: -
Scaling: -
Max
4194303.000
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Data type: FloatingPoint32
Data set: -
Factory setting
1000 [ms]
Data type: Unsigned32
Data set: -
Factory setting
1
Data type: FloatingPoint32
Data set: -
Factory setting
1.000