Siemens CU230P-2 HVAC Parameter Manual page 185

Sinamics g120 control units
Hide thumbs Also See for CU230P-2 HVAC:
Table of Contents

Advertisement

p1478[0...n]
CI: Speed controller integrator setting value / n_ctr integ_setVal
Access level: 3
Can be changed: T
Min
-
Description:
Sets the signal source for the integrator setting value for the velocity controller.
The signal to set this integrator setting value is interconnected via p1477.
Dependency:
The setting value of the speed controller integrator is weighted with the scaling factor of the signal source in p1479.
If p1478 is interconnected to the integral output of the speed controller (r1482), then after the magnetizing time
(r0346) and if the speed controller is enabled, the integral component of the controller is set to the last value before
the pulse inhibit. This value is set if no setting command (p1477) is interconnected or, at the instant that the pulses
were inhibited, a setting command is available, which is not deactivated up to the next time that the pulses are
inhibited. For encoderless vector control, in addition p1400.1 should be set to 1 so that when the drive is stopped,
the integral component of the speed controller is not controlled down to zero.
In order that when setting the integrator output, only the static torque is detected, we recommend that the accelerat-
ing torque is completely pre-controlled (e.g. p1496).
If p1478 is interconnected to another output other than r1482, then after magnetizing and speed controller enable,
the integral output is set once if the setting command is not interconnected (p1477 = 0).
Refer to: p1477, p1479
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1479[0...n]
CI: Speed controller integrator setting value scaling / n_ctrl I_val scal
Access level: 4
Can be changed: T
Min
-
Description:
Sets the signal source for scaling the integrator setting value (p1478) of the speed controller.
Dependency:
Refer to: p1477, p1478
r1482
CO: Speed controller I torque output / n_ctrl I-M_output
Access level: 3
Unit: [Nm]
Description:
Displays the torque setpoint at the output of the I speed controller.
p1486[0...n]
CI: Droop compensation torque / Droop M_comp
Access level: 3
Can be changed: T
Min
-
Description:
Sets the signal source for the compensation torque to be output within the droop calculation.
p1487[0...n]
Droop compensation torque scaling / Droop M_comp scal
Access level: 3
Can be changed: U, T
Min
-2000.0 [%]
Description:
Sets the scaling for the compensation torque within the droop calculation.
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Calculated: -
Scaling: p2003
Max
-
Calculated: -
Scaling: PERCENT
Max
-
Calculated: -
Scaling: p2003
Calculated: -
Scaling: p2003
Max
-
Calculated: -
Scaling: PERCENT
Max
2000.0 [%]
Parameters
List of Parameters
Data type: U32 / FloatingPoint32
Data set: CDS, p0170
Factory setting
0
Data type: U32 / FloatingPoint32
Data set: CDS, p0170
Factory setting
1
Data type: FloatingPoint32
Data set: -
Data type: U32 / FloatingPoint32
Data set: CDS, p0170
Factory setting
0
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
100.0 [%]
1-185

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for: