Signal targets for STW1 in Interface Mode SINAMICS (p2038 = 0)
Signal
Meaning
= ON (pulses can be enabled)
STW1.0
0 = OFF1 (braking with ramp-function generator, then pulse cancllation & ready-to-power-up)
1 = No OFF2 (enable is possible)
STW1.1
0 = OFF2 (immediate pulse cancellation and power-on inhibit)
1 = No OFF3 (enable is possible)
STW1.2
0 = OFF3 (braking with the OFF3 ramp p1135, then pulse cancellation and power-on inhibit)
1 = Enable operation (pulses can be enabled)
STW1.3
0 = Inhibit operation (cancel pulses)
1 = Operating condition (the ramp-function generator can be enabled)
STW1.4
0 = Inhibit ramp-function generator (set the ramp-function generator output to zero)
1 = Enable the ramp-function generator
STW1.5
0 = Stop the ramp-function generator (freeze the ramp-function generator output)
1 = Enable setpoint
STW1.6
0 = Inhibit setpoint (set the ramp-function generator input to zero)
STW1.7
= Acknowledge faults
STW1.8
Reserved
STW1.9
Reserved
STW1.10
1 = Control via PLC
STW1.11
1 = Dir of rot reversal
Reserved
STW1.12
STW1.13
1 = Motorized potentiometer, setpoint, raise
STW1.14
1 = Motorized potentiometer, setpoint, lower
STW1.15
Reserved
Used in telegrams 1, 352.
<1>
<2>
Bit 10 in STW1 must be set to ensure that the drive accepts the process data.
1
2
PROFIdrive / PROFIBUS
STW1 control word interconnection (p2038 = 0)
<2>
3
4
[Function diagram]
[Function diagram]
Interconnection
internal control word
parameters
p0840[0] = r2090.0
[2501.3]
Sequence control
p0844[0] = r2090.1
[2501.3]
Sequence control
p0848[0] = r2090.2
[2501.3]
Sequence control
Sequence control
p0852[0] = r2090.3
[2501.3]
p1140[0] = r2090.4
[2501.3]
[3060] [3070] [3080]
p1141[0] = r2090.5
[2501.3]
p1142[0] = r2090.6
[2501.3]
[3060] [3070] [3080]
p2103[0] = r2090.7
[2546.1]
-
-
-
-
p0854[0] = r2090.10
[2501.3]
p1113[0] = r2090.11
[2505.3]
-
-
p1035[0] = r2090.13
[2505.3]
p1036[0] = r2090.14
[2505.3]
-
-
5
6
Function diagram
FP_2442_97_51.vsd
G120 CU230P-2 DP
29.10.2009
V4.3
<1>
Inverted
signal target
-
-
-
-
-
[3060] [3070]
-
-
[8060]
-
-
-
-
-
[2501]
-
[3040]
-
-
-
[3020]
-
[3020]
-
-
-
7
8
- 2442 -