Faults and Alarms
List of Faults and Alarms
A07980
Drive: Rotating measurement activated
Reaction:
NONE
Acknowledge:
NONE
Cause:
The rotating measurement (automatic speed controller optimization) is activated.
The rotating measurement is carried out at the next power-on command.
See also: p1960 (Rotating measurement selection)
Remedy:
None necessary.
The alarm disappears automatically after the speed controller optimization has been successfully completed or for
the setting p1900 = 0.
A07981
Drive: Enable signals for the rotating measurement missing
Reaction:
NONE
Acknowledge:
NONE
Cause:
The rotating measurement cannot be started due to missing enable signals.
Remedy:
- acknowledge faults that are present.
- establish missing enable signals.
See also: r0002 (Drive operating display), r0046 (Missing enable sig)
F07983
Drive: Rotating measurement saturation characteristic
Reaction:
OFF1 (NONE, OFF2)
Acknowledge:
IMMEDIATELY
Cause:
A fault has occurred while determining the saturation characteristic.
Fault value (r0949, interpret decimal):
1: The speed did not reach a steady-state condition.
2: The rotor flux did not reach a steady-state condition.
3: The adaptation circuit did not reach a steady-state condition.
4: The adaptation circuit was not enabled.
5: Field weakening active.
6: The speed setpoint was not able to be approached as the minimum limiting is active.
7: The speed setpoint was not able to be approached as the suppression (skip) bandwidth is active.
8: The speed setpoint was not able to be approached as the maximum limiting is active.
9: Several values of the determined saturation characteristic are not plausible.
10: Saturation characteristic could not be sensibly determined because load torque too high.
Remedy:
Re fault value = 1:
- the total drive moment of inertia is far higher than that of the motor (p0341, p0342).
Deselect rotating measurement (p1960), enter the moment of inertia p0342, recalculate the speed controller p0340
= 4 and repeat the measurement.
Re fault value = 1 ... 2:
- increase the measuring speed (p1961) and repeat the measurement.
Re fault value = 1 ... 4:
- check the motor parameters (rating plate data). After the change: Calculate p0340 = 3.
- check the moment of inertia (p0341, p0342). After the change: Calculate p0340 = 3.
- carry out a motor data identification routine (p1910).
- if required, reduce the dynamic factor (p1967 < 25 %).
Re fault value = 5:
- the speed setpoint (p1961) is too high. Reduce the speed.
Re fault value = 6:
- adapt the speed setpoint (p1961) or minimum limiting (p1080).
Re fault value = 7:
- adapt the speed setpoint (p1961) or suppression (skip) bandwidths (p1091 ... p1094, p1101).
Re fault value = 8:
- adapt the speed setpoint (p1961) or maximum limit (p1082, p1083 and p1086).
Re fault value = 9, 10:
- the measurement was carried out at an operating point where the load torque is too high. Select a more suitable
operating point, either by changing the speed setpoint (p1961) or by reducing the load torque. The load torque may
not be varied while making measurements.
Note:
The saturation characteristic identification routine can be disabled using p1959.1.
See also: p1959 (Rotating measurement configuration)
3-628
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009