p1039[0...n]
BI: Motorized potentiometer inversion / Mop inversion
Access level: 3
Can be changed: T
Min
-
Description:
Sets the signal source to invert the minimum speed/velocity or the maximum speed/velocity for the motorized
potentiometer.
Dependency:
Refer to: p1037, p1038
Note:
The inversion is only active during "motorized potentiometer raise" or "motorized potentiometer lower".
p1040[0...n]
Motorized potentiometer starting value / Mop start value
Access level: 2
Can be changed: U, T
Min
-210000.000 [rpm]
Description:
Sets the starting value for the motorized potentiometer. This starting value becomes effective after the drive has
been powered up.
Dependency:
Only effective if p1030.0 = 0.
Refer to: p1030
p1041[0...n]
BI: Motorized potentiometer manual/automatic / Mop manual/auto
Access level: 3
Can be changed: T
Min
-
Description:
Sets the signal source to change over from manual to automatic when using a motorized potentiometer.
In the manual mode, the setpoint is changed using two signals - raise and lower. In the automatic mode, the set-
point must be interconnected via a connector input.
Dependency:
Refer to: p1030, p1035, p1036, p1042
Note:
The effectiveness of the internal ramp-function generator can be set in automatic mode.
p1042[0...n]
CI: Motorized potentiometer automatic setpoint / Mop auto setpoint
Access level: 3
Can be changed: T
Min
-
Description:
Sets the signal source for the setpoint of the motorized potentiometer in the automatic mode.
Dependency:
Refer to: p1041
p1043[0...n]
BI: Motorized potentiometer accept setpoint / Mop accept set val
Access level: 3
Can be changed: T
Min
-
Description:
Sets the signal source to accept the setting value for the motorized potentiometer.
Dependency:
Refer to: p1044
Note:
The setting value (CI: p1044) becomes effective for a 0/1 edge of the setting command (BI: p1043).
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Calculated: -
Scaling: -
Max
-
Calculated: -
Scaling: -
Max
210000.000 [rpm]
Calculated: -
Scaling: -
Max
-
Calculated: -
Scaling: p2000
Max
-
Calculated: -
Scaling: -
Max
-
Parameters
List of Parameters
Data type: U32 / Binary
Data set: CDS, p0170
Factory setting
0
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0.000 [rpm]
Data type: U32 / Binary
Data set: CDS, p0170
Factory setting
0
Data type: U32 / FloatingPoint32
Data set: CDS, p0170
Factory setting
0
Data type: U32 / Binary
Data set: CDS, p0170
Factory setting
0
1-131

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu230p-2 dpCu230p-2 can

Table of Contents