Siemens CU230P-2 HVAC Parameter Manual page 216

Sinamics g120 control units
Hide thumbs Also See for CU230P-2 HVAC:
Table of Contents

Advertisement

Parameters
List of Parameters
p1900
Motor data identification and rotating measurement / MotID and rot meas
Access level: 2
Can be changed: C(1), T
Min
0
Description:
Sets the motor data identification and speed controller optimization.
p1900 = 0:
Function inhibited.
p1900 = 1:
Sets p1910 = 1 and p1960 = 0, 1 depending on p1300
When the drive enable signals are present, a motor data identification routine is carried out at standstill with the
next power-on command. Current flows through the motor which means that it can align itself by up to a quarter of
a revolution.
With the following power-on command, a rotating motor data identification routine is carried out - and in addition, a
speed controller optimization by making measurements at different motor speeds.
p1900 = 2:
Sets p1910 = 1 and p1960 = 0
When the drive enable signals are present, a motor data identification routine is carried out at standstill with the
next power-on command. Current flows through the motor which means that it can align itself by up to a quarter of
a revolution.
p1900 = 3:
Sets p1960 = 0, 1 depending on p1300
This setting should only be selected if the motor data identification was already carried out at standstill.
When the drive enable signals are present, with the next power-on command, a rotating motor data identification
routine is carried out - and in addition, speed controller optimization by taking measurements at different motor
speeds.
Value:
0:
1:
2:
3:
Dependency:
Refer to: p1300, p1910, p1960
Refer to: A07980, A07981, F07983, F07984, F07985, F07986, F07988, F07990, A07991
Notice:
To permanently accept the determined settings they must be saved in a non-volatile fashion (p0971).
For p0014 = 1, the following applies:
After the value has been modified, no further parameter modifications can be made and the status is shown in
r3996. Modifications can be made again when r3996 = 0.
Note:
The motor and control parameters are only optimally set when both measurements are carried out (initially at stand-
still, and then with the motor rotating).
An appropriate alarm is output when the parameter is set.
The power-on command must remain set during a measurement and after the measurement has been completed,
the drive automatically resets it.
The duration of the measurements can lie between 0.3 s and several minutes. This time is, for example, influenced
by the motor size and the mechanical conditions.
p1900 is automatically set to 0 after the motor data identification routine has been completed.
1-216
Inhibited
Identify motor data at standstill and with motor rotating
Identify motor data at standstill
Identify motor data with motor rotating
Calculated: -
Scaling: -
Max
3
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Data type: Integer16
Data set: -
Factory setting
0
© Siemens AG 2009 All Rights Reserved