Siemens CU230P-2 HVAC Parameter Manual page 337

Sinamics g120 control units
Hide thumbs Also See for CU230P-2 HVAC:
Table of Contents

Advertisement

p11058
Free tec_ctrl 0 setpoint ramp-down time / Ftec0 setp t_r-dn
Access level: 2
Can be changed: U, T
Min
0.00 [s]
Description:
Sets the ramp-down time for the free technology controller 0.
Dependency:
Refer to: p11057
Note:
The ramp-down time is referred to 100 %.
r11060
CO: Free tec_ctrl 0 setpoint after ramp-function generator / Ftec0 setp aft RFG
Access level: 2
Unit: [%]
Description:
Display and connector output for the setpoint after the ramp-function generator of the free technology controller 0.
p11064
CI: Free tec_ctrl 0 actual value signal source / Ftec0 act v s_s
Access level: 2
Can be changed: U, T
Min
-
Description:
Sets the signal source for the actual value of the free technology controller 0.
p11065
Free tec_ctrl 0 actual value smoothing time constant / Ftec0 act v T
Access level: 2
Can be changed: U, T
Min
0.00 [s]
Description:
Sets the smoothing time constant (PT1) for the actual value of the free technology controller 0.
p11067
Free tec_ctrl 0 actual value upper limit / Ftec0 act v up lim
Access level: 3
Can be changed: U, T
Min
-200.00 [%]
Description:
Sets the upper limit for the actual value signal of the free technology controller 0.
Dependency:
Refer to: p11064
p11068
Free tec_ctrl 0 actual value lower limit / Ftec0 act v lo lim
Access level: 3
Can be changed: U, T
Min
-200.00 [%]
Description:
Sets the lower limit for the actual value signal of the free technology controller 0.
Dependency:
Refer to: p11064
p11071
Free tec_ctrl 0 actual value inversion / Ftec0 act v inv
Access level: 3
Can be changed: T
Min
0
Description:
Sets the inversion of the actual value signal of the free technology controller 0.
Value:
0:
1:
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
No inversion
Inversion
Calculated: -
Scaling: -
Max
650.00 [s]
Calculated: -
Scaling: PERCENT
Calculated: -
Scaling: PERCENT
Max
-
Calculated: -
Scaling: -
Max
60.00 [s]
Calculated: -
Scaling: PERCENT
Max
200.00 [%]
Calculated: -
Scaling: PERCENT
Max
200.00 [%]
Calculated: -
Scaling: -
Max
1
Parameters
List of Parameters
Data type: FloatingPoint32
Data set: -
Factory setting
1.00 [s]
Data type: FloatingPoint32
Data set: -
Data type: U32 / FloatingPoint32
Data set: -
Factory setting
0
Data type: FloatingPoint32
Data set: -
Factory setting
0.00 [s]
Data type: FloatingPoint32
Data set: -
Factory setting
100.00 [%]
Data type: FloatingPoint32
Data set: -
Factory setting
-100.00 [%]
Data type: Integer16
Data set: -
Factory setting
0
1-337