Siemens CU230P-2 HVAC Parameter Manual page 605

Sinamics g120 control units
Hide thumbs Also See for CU230P-2 HVAC:
Table of Contents

Advertisement

F01505 (A)
BICO: Interconnection cannot be established
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
A PROFIdrive telegram has been set (p0922).
An interconnection contained in the telegram was not able to be established.
Fault value (r0949, interpret decimal):
Parameter receiver that should be changed.
Remedy:
Establish another interconnection.
F01510
BICO: Signal source is not float type
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The requested connector output does not have the correct data type. This interconnection is not established.
Fault value (r0949, interpret decimal):
Parameter number to which an interconnection should be made (connector output).
Remedy:
Interconnect this connector input with a connector output having a float data type.
F01511 (A)
BICO: Interconnection between different normalizations
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The requested interconnection was established. However, a conversion is made between the BICO output and BICO
input using the reference values.
- the BICO output has different normalized units than the BICO input.
- message only for interconnections within a drive object.
Example:
The BICO output has, as normalized unit, voltage and the BICO input has current.
This means that the factor p2002 (contains the reference value for current) / p2001 (contains the reference value for
voltage) is calculated between the BICO output and BICO input.
Fault value (r0949, interpret decimal):
Parameter number of the BICO input (signal sink).
Remedy:
No correction needed.
F01512
BICO: No normalization available
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
An attempt was made to determine a conversion factor for a normalization that does not exist.
Fault value (r0949, interpret decimal):
Unit (e.g. corresponding to SPEED) for which an attempt was made to determine a factor.
Remedy:
Apply normalization or check the transfer value.
A01514 (F)
BICO: Error when writing during a reconnect
Reaction:
NONE
Acknowledge:
NONE
Cause:
During a reconnect operation (e.g. while booting or downloading - but can also occur in normal operation) a param-
eter was not able to be written to.
Example:
When writing to a double word BICO input in the second index, the memory areas overlap (e.g. p8861). The param-
eter is then reset to the factory setting.
Alarm value (r2124, interpret decimal):
Parameter number of the BICO input (signal sink).
Remedy:
None necessary.
F01515 (A)
BICO: Writing to parameter not permitted as the master control is active
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
While changing the number of CDS or when copying from CDS, the master control was active.
Remedy:
None necessary.
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Faults and Alarms
List of Faults and Alarms
3-605