p8630[0...2]
CAN virtual objects / Virtual objects
CU230P-2 CAN
Access level: 3
Can be changed: U, T
Min
0
Description:
Activating access to parameters via manufacturer-specific CANopen objects and setting for the subindex area
(index 1) and the parameter area (index 2) when using virtual objects.
This means that it is possible to access all SINAMICS parameters via CAN.
Index 0:
0: Not possible to access virtual CANopen objects
1: Possible to access virtual CANopen objects
Index 1 (sub-index area):
0: 0 ... 255
1: 256 ... 511
2: 512 ... 767
3: 768 ... 1023
Index 2 (parameter area):
0: 1 ... 9999
1: 10000 ... 19999
2: 20000 ... 29999
3: 30000 ... 39999
Index:
[0] = Drive object selection
[1] = Sub-index range
[2] = Parameter range
p8641
CAN Abort Connection Option Code / Abort con opt code
CU230P-2 CAN
Access level: 3
Can be changed: T
Min
0
Description:
Sets the drive behavior if a CAN communication error occurs.
Value:
0:
1:
2:
3:
Dependency:
Refer to: F08700
r8680[0...36]
CAN Diagnosis Hardware / Diagnostics HW
CU230P-2 CAN
Access level: 3
Unit: -
Description:
Displays the register of the CAN controller C_CAN:
Register, Message Interface Register and Message Handler Register - referred to the CAN protocol.
Index:
[0] = Control register
[1] = Status register
[2] = Error counter
[3] = Bit timing register
[4] = Interrupt register
[5] = Test register
[6] = Baud rate prescaler extension register
[7] = Interface 1 command request register
[8] = Interface 1 command mask register
Note:
A description of the individual registers of the C_CAN controller can be taken from "C_CAN User's Manual".
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
No response
OFF1
OFF2
OFF3
Calculated: -
Scaling: -
Max
65535
Calculated: -
Scaling: -
Max
3
Calculated: -
Scaling: -
Parameters
List of Parameters
Data type: Unsigned16
Data set: -
Factory setting
0
Data type: Integer16
Data set: -
Factory setting
3
Data type: Unsigned16
Data set: -
1-315