Parameters
List of Parameters
p0844[0...n]
BI: 1. OFF2 / 1. OFF2
CU230P-2 CAN
Access level: 3
CU230P-2 HVAC
Can be changed: T
Min
-
Description:
Sets the signal source for the 1st OC/OFF2.
The AND logic operation of the 1st OC/OFF2 and 2nd OC/OFF2 results in control word 1, bit 1 (OC/OFF2).
Caution:
When "master control from PC" is activated, this binector input is ineffective.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
Bit 1 = 0: OC/OFF2 (immediate pulse suppression and switching on inhibited)
Bit 1 = 1: No OC/OFF2 (enable is possible)
OC: Operating condition
p0844[0...n]
BI: 1. OFF2 / 1. OFF2
CU230P-2 DP
Access level: 3
Can be changed: T
Min
-
Description:
Sets the signal source for the 1st OC/OFF2.
The AND logic operation of the 1st OC/OFF2 and 2nd OC/OFF2 results in control word 1, bit 1 (OC/OFF2).
Caution:
When "master control from PC" is activated, this binector input is ineffective.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
Bit 1 = 0: OC/OFF2 (immediate pulse suppression and switching on inhibited)
Bit 1 = 1: No OC/OFF2 (enable is possible)
OC: Operating condition
p0845[0...n]
BI: 2. OFF2 / 2. OFF2
Access level: 3
Can be changed: T
Min
-
Description:
Sets the signal source for the 2nd OC/OFF2.
The AND logic operation of the 1st OC/OFF2 and 2nd OC/OFF2 results in control word 1, bit 1 (OC/OFF2).
Note:
Bit 1 = 0: OC/OFF2 (immediate pulse suppression and switching on inhibited)
Bit 1 = 1: No OC/OFF2 (enable is possible)
OC: Operating condition
1-110
Calculated: -
Scaling: -
Max
-
Calculated: -
Scaling: -
Max
-
Calculated: -
Scaling: -
Max
-
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Data type: U32 / Binary
Data set: CDS, p0170
Factory setting
1
Data type: U32 / Binary
Data set: CDS, p0170
Factory setting
2090.1
Data type: U32 / Binary
Data set: CDS, p0170
Factory setting
1