Siemens CU230P-2 HVAC Parameter Manual page 316

Sinamics g120 control units
Hide thumbs Also See for CU230P-2 HVAC:
Table of Contents

Advertisement

Parameters
List of Parameters
p8684
CAN NMT state after booting / NMT state boot
CU230P-2 CAN
Access level: 3
Can be changed: T
Min
4
Description:
Sets the CANopen NMT state that is effective after booting.
Value:
4:
5:
127:
Dependency:
Refer to: p8685
Note:
Booting in the NMT state pre-operational corresponds to the CANopen standard
p8685
CAN NMT states / NMT states
CU230P-2 CAN
Access level: 3
Can be changed: C(1), U, T
Min
0
Description:
Sets and displays the CANopen NMT state.
Value:
0:
4:
5:
127:
128:
129:
Note:
The value 0 (initialization) is only displayed and cannot be set.
p8700[0...1]
CAN Receive PDO 1 / Receive PDO 1
CU230P-2 CAN
Access level: 3
Can be changed: C(3), T
Min
0000 hex
Description:
Sets the communication parameters for CANopen Receive Process Data Object 1 (RPDO 1).
Index:
[0] = PDO COB-ID
[1] = PDO transmission type
Dependency:
A valid COB-ID can only be set for the available (existing) channel.
Refer to: p8741
Note:
Corresponds to the CANopen object 1400 hex + 40 hex * x (x: Drive number 0 ... 7).
Transmission types 0, 1, FE and FF can be set.
PDO: Process Data Object
p8701[0...1]
CAN Receive PDO 2 / Receive PDO 2
CU230P-2 CAN
Access level: 3
Can be changed: C(3), T
Min
0000 hex
Description:
Sets the communication parameters for CANopen Receive Process Data Object 2 (RPDO 2).
Index:
[0] = PDO COB-ID
[1] = PDO transmission type
Dependency:
A valid COB-ID can only be set for the available (existing) channel.
Refer to: p8741
Note:
Corresponds to the CANopen object 1401 hex + 40 hex * x (x: Drive number 0 ... 7).
Transmission types 0, 1, FE and FF can be set.
PDO: Process Data Object
1-316
Stopped
Operational
Pre-operational
Initializing
Stopped
Operational
Pre-operational
Reset node
Reset Communication
Calculated: -
Scaling: -
Max
127
Calculated: -
Scaling: -
Max
129
Calculated: -
Scaling: -
Max
8000 06DF hex
Calculated: -
Scaling: -
Max
8000 06DF hex
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Data type: Integer16
Data set: -
Factory setting
127
Data type: Integer16
Data set: -
Factory setting
127
Data type: Unsigned32
Data set: -
Factory setting
8000 06DF hex
Data type: Unsigned32
Data set: -
Factory setting
8000 06DF hex
© Siemens AG 2009 All Rights Reserved

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu230p-2 dpCu230p-2 can

Table of Contents