p1322[0...n]
V/f control programmable characteristic frequency 2 / Vf char f2
Access level: 3
Can be changed: U, T
Min
0.00 [Hz]
Description:
The programmable characteristic for the V/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the voltage of the second point along the characteristic.
Dependency:
The following applies to the frequency values: p1320 <= p1322 <= p1324 <= p1326. Otherwise, a standard charac-
teristic is used that contains the rated motor operating point.
Refer to: p1310, p1311, p1320, p1321, p1323, p1324, p1325, p1326, p1327
p1323[0...n]
V/f control programmable characteristic voltage 2 / Vf char U2
Access level: 3
Can be changed: U, T
Min
0.0 [Vrms]
Description:
The programmable characteristic for the V/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the voltage of the second point along the characteristic.
Dependency:
Refer to: p1310, p1311, p1320, p1321, p1322, p1324, p1325, p1326, p1327
p1324[0...n]
V/f control programmable characteristic frequency 3 / Vf char f3
Access level: 3
Can be changed: U, T
Min
0.00 [Hz]
Description:
The programmable characteristic for the V/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the voltage of the third point along the characteristic.
Dependency:
The following applies to the frequency values: p1320 <= p1322 <= p1324 <= p1326. Otherwise, a standard charac-
teristic is used that contains the rated motor operating point.
Refer to: p1310, p1311, p1320, p1321, p1322, p1323, p1325, p1326, p1327
p1325[0...n]
V/f control programmable characteristic voltage 3 / Vf char U3
Access level: 3
Can be changed: U, T
Min
0.0 [Vrms]
Description:
The programmable characteristic for the V/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the voltage of the third point along the characteristic.
Dependency:
Refer to: p1310, p1311, p1320, p1321, p1322, p1323, p1324, p1326, p1327
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Calculated: p0340 = 1
Scaling: -
Max
3000.00 [Hz]
Calculated: p0340 = 1
Scaling: -
Max
10000.0 [Vrms]
Calculated: p0340 = 1
Scaling: -
Max
3000.00 [Hz]
Calculated: p0340 = 1
Scaling: -
Max
10000.0 [Vrms]
Parameters
List of Parameters
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0.00 [Hz]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0.0 [Vrms]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0.00 [Hz]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0.0 [Vrms]