Parameters
List of Parameters
p1488[0...n]
Droop input source / Droop input source
Access level: 3
Can be changed: U, T
Min
0
Description:
Sets the source for droop feedback.
Value:
0:
1:
2:
3:
Dependency:
Refer to: p1489, r1490, p1492
p1489[0...n]
Droop feedback scaling / Droop scaling
Access level: 3
Can be changed: U, T
Min
0.000
Description:
Sets the scaling for the droop feedback
Dependency:
Refer to: p1488, r1490, p1492
Note:
Example:
A value of 0.05 means that for a torque equal to the rated motor torque, the rated motor speed is reduced by 5 %.
r1490
CO: Droop feedback speed reduction / Droop n_reduction
Access level: 3
Unit: [rpm]
Description:
Displays the output signal of the droop calculation. The droop feedback result is subtracted from the speed setpoint
when activated (p1492).
Dependency:
Refer to: p1488, p1489, p1492
p1492[0...n]
BI: Droop feedback enable / Droop enable
Access level: 3
Can be changed: U, T
Min
-
Description:
Enables the droop to be applied to the speed/velocity setpoint.
Dependency:
Refer to: p1488, p1489, r1490
Note:
Even when not enabled, the droop speed is calculated but not subtracted from the setpoint speed. This makes it
possible to subtract the result of this calculation from the speed of another drive.
r1493
CO: Moment of inertia, total / M_inertia total
Access level: 3
Unit: [kgm²]
Description:
Displays the parameterized total moment of inertia ((p0341 * p0342) * p1496).
1-186
Droop feedback not connected
Droop from torque setpoint
Droop from speed controller output
Droop from integral output, speed controller
Calculated: -
Scaling: -
Max
3
Calculated: -
Scaling: -
Max
0.500
Calculated: -
Scaling: p2000
Calculated: -
Scaling: -
Max
-
Calculated: -
Scaling: -
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Data type: Integer16
Data set: DDS, p0180
Factory setting
0
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0.050
Data type: FloatingPoint32
Data set: -
Data type: U32 / Binary
Data set: CDS, p0170
Factory setting
0
Data type: FloatingPoint32
Data set: -
© Siemens AG 2009 All Rights Reserved