Siemens CU230P-2 HVAC Parameter Manual page 137

Sinamics g120 control units
Hide thumbs Also See for CU230P-2 HVAC:
Table of Contents

Advertisement

p1085[0...n]
CI: Speed limit in positive direction of rotation / n_limit pos
Access level: 3
Can be changed: T
Min
-
Description:
Sets the signal source for the speed limit of the positive direction.
p1086[0...n]
CO: Speed limit in negative direction of rotation / n_limit neg
Access level: 3
Can be changed: U, T
Min
-210000.000 [rpm]
Description:
Sets the speed limit for the negative direction.
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
r1087
CO: Speed limit negative effective / n_limit neg eff
Access level: 3
Unit: [rpm]
Description:
Displays the effective negative speed limit.
Dependency:
Refer to: p1082, p1086, p1088
p1088[0...n]
CI: Speed limit in negative direction of rotation / n_limit neg
Access level: 3
Can be changed: T
Min
-
Description:
Sets the signal source for the speed/velocity limit of the negative direction.
p1091[0...n]
Skip speed 1 / n_skip 1
Access level: 3
Can be changed: U, T
Min
0.000 [rpm]
Description:
Sets skip speed 1.
Dependency:
Refer to: p1092, p1093, p1094, p1101
Note:
The skip (suppression) speeds can be used to prevent the effects of mechanical resonance.
p1092[0...n]
Skip speed 2 / n_skip 2
Access level: 3
Can be changed: U, T
Min
0.000 [rpm]
Description:
Sets skip speed 2.
Dependency:
Refer to: p1091, p1093, p1094, p1101
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Calculated: -
Scaling: p2000
Max
-
Calculated: -
Scaling: p2000
Max
0.000 [rpm]
Calculated: -
Scaling: p2000
Calculated: -
Scaling: p2000
Max
-
Calculated: -
Scaling: p2000
Max
210000.000 [rpm]
Calculated: -
Scaling: p2000
Max
210000.000 [rpm]
Parameters
List of Parameters
Data type: U32 / FloatingPoint32
Data set: CDS, p0170
Factory setting
1083[0]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
-210000.000 [rpm]
Data type: FloatingPoint32
Data set: -
Data type: U32 / FloatingPoint32
Data set: CDS, p0170
Factory setting
1086[0]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0.000 [rpm]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0.000 [rpm]
1-137