Siemens CU230P-2 HVAC Parameter Manual page 336

Sinamics g120 control units
Hide thumbs Also See for CU230P-2 HVAC:
Table of Contents

Advertisement

Parameters
List of Parameters
p11000
BI: Free tec_ctrl 0 enable / Ftec0 enab
Access level: 2
Can be changed: U, T
Min
-
Description:
Sets the signal source to switch in/switch out the free technology controller 0.
1 signal: The technology controller is switched in.
0 signal: The technology controller is switched out.
p11028
Free tec_ctrl 0 sampling time / Ftec0 t_samp
Access level: 3
Can be changed: T
Min
0
Description:
Sets the sampling time for the free technology controller 0.
Value:
0:
1:
2:
3:
4:
r11049.0...11
CO/BO: Free tec_ctrl 0 status word / Ftec0 stat_word
Access level: 3
Unit: -
Description:
Displays the status word of the free technology controller 0.
Bit field:
Bit
Signal name
00
Deactivated
01
Limited
08
Actual value at the minimum
09
Actual value at the maximum
10
Output at the minimum
11
Output at the maximum
p11053
CI: Free tec_ctrl 0 setpoint signal source / Ftec0 setp s_s
Access level: 2
Can be changed: U, T
Min
-
Description:
Sets the signal source for the setpoint of the free technology controller 0.
p11057
Free tec_ctrl 0 setpoint ramp-up time / Ftec0 setp t_r-up
Access level: 2
Can be changed: U, T
Min
0.00 [s]
Description:
Sets the ramp-up time for the free technology controller 0.
Dependency:
Refer to: p11058
Note:
The ramp-up time is referred to 100 %.
1-336
Reserved
128 ms
256 ms
512 ms
1024 ms
Calculated: -
Scaling: -
Max
-
Calculated: -
Scaling: -
Max
4
Calculated: -
Scaling: -
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Scaling: PERCENT
Max
-
Calculated: -
Scaling: -
Max
650.00 [s]
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Data type: U32 / Binary
Data set: -
Factory setting
0
Data type: Integer16
Data set: -
Factory setting
2
Data type: Unsigned32
Data set: -
0 signal
No
No
No
No
No
No
Data type: U32 / FloatingPoint32
Data set: -
Factory setting
0
Data type: FloatingPoint32
Data set: -
Factory setting
1.00 [s]