r0837.0...1
CO/BO: Drive Data Set DDS selected / DDS selected
Access level: 3
Unit: -
Description:
Displays the drive data set (DDS) selected via the binector input.
Bit field:
Bit
Signal name
00
DDS select. bit 0
01
DDS select. bit 1
Dependency:
Refer to: r0051, p0820, p0821
Note:
Drive data sets are selected via binector input p0820 and following.
The currently effective drive data set is displayed in r0051.
If there is only one data set, then a value of 0 is displayed in this parameter and not the selection via binector inputs.
p0840[0...n]
BI: ON/OFF1 / ON/OFF1
CU230P-2 CAN
Access level: 3
CU230P-2 HVAC
Can be changed: T
Min
-
Description:
Sets the signal source for control word 1 bit 0 (ON/OFF1).
Dependency:
Refer to: p1055, p1056
Notice:
For BI: p0840 = 0 signal, the motor can be moved, jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that originally powered up can also power down again.
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
For drives with closed-loop speed control (p1300 = 20), the following applies:
- Bit 0 = 0: OFF1 (braking with the ramp-function generator, then pulse suppression and switching on inhibited)
For drives with closed-loop torque control (p1300 = 22), the following applies:
- Bit 0 = 0: Immediate pulse suppression
For drives with closed-loop torque control (activated using p1501), the following applies:
- Bit 0 = 0: No dedicated braking response, but pulse suppression when standstill is detected (p1226, p1227)
For drives with closed-loop speed/torque control, the following applies:
- Bit 0 = 0/1: ON (pulses can be enabled)
p0840[0...n]
BI: ON/OFF1 / ON/OFF1
CU230P-2 DP
Access level: 3
Can be changed: T
Min
-
Description:
Sets the signal source for control word 1 bit 0 (ON/OFF1).
Dependency:
Refer to: p1055, p1056
Notice:
For BI: p0840 = 0 signal, the motor can be moved, jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that originally powered up can also power down again.
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
For drives with closed-loop speed control (p1300 = 20), the following applies:
- Bit 0 = 0: OFF1 (braking with the ramp-function generator, then pulse suppression and switching on inhibited)
For drives with closed-loop torque control (p1300 = 22), the following applies:
- Bit 0 = 0: Immediate pulse suppression
For drives with closed-loop torque control (activated using p1501), the following applies:
- Bit 0 = 0: No dedicated braking response, but pulse suppression when standstill is detected (p1226, p1227)
For drives with closed-loop speed/torque control, the following applies:
- Bit 0 = 0/1: ON (pulses can be enabled)
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Calculated: -
Scaling: -
1 signal
On
On
Calculated: -
Scaling: -
Max
-
Calculated: -
Scaling: -
Max
-
Parameters
List of Parameters
Data type: Unsigned8
Data set: -
0 signal
Off
Off
Data type: U32 / Binary
Data set: CDS, p0170
Factory setting
722.0
Data type: U32 / Binary
Data set: CDS, p0170
Factory setting
2090.0
FP
-
-