Siemens CU230P-2 HVAC Parameter Manual page 254

Sinamics g120 control units
Hide thumbs Also See for CU230P-2 HVAC:
Table of Contents

Advertisement

Parameters
List of Parameters
r2134[0...63]
Alarm value for float values / Alarm value float
Access level: 3
Unit: -
Description:
Displays additional information about the active alarm for float values.
Dependency:
Refer to: r2110, r2122, r2123, r2124, r2125, r2145, r2146
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
r2135.12...15
CO/BO: Status word faults/alarms 2 / ZSW fault/alarm 2
Access level: 2
Unit: -
Description:
Displays the second status word of faults and alarms.
Bit field:
Bit
Signal name
12
Fault motor overtemperature
13
Fault power unit thermal overload
14
Alarm motor overtemperature
15
Alarm power unit thermal overload
r2136[0...63]
Fault time removed in days / t_flt resolv. days
Access level: 3
Unit: -
Description:
Displays the system runtime in days when the fault was removed.
Dependency:
Refer to: r0945, r0947, r0948, r0949, r2109, r2130, r2133, p8401
Notice:
The time comprises r2136 (days) and r2109 (milliseconds).
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
r2138.7...15
CO/BO: Control word faults/alarms / STW fault/alarm
Access level: 2
Unit: -
Description:
Displays the control word of the faults and alarms.
Bit field:
Bit
Signal name
07
Acknowledge fault
10
External alarm 1 (A07850) effective
11
External alarm 2 (A07851) effective
12
External alarm 3 (A07852) effective
13
External fault 1 (F07860) effective
14
External fault 2 (F07861) effective
15
External fault 3 (F07862) effective
Dependency:
Refer to: p2103, p2104, p2105, p2106, p2107, p2108, p2112, p2116, p2117, p3110, p3111, p3112
1-254
Calculated: -
Scaling: -
Calculated: -
Scaling: -
1 signal
Yes
Yes
Yes
Yes
Calculated: -
Scaling: -
Calculated: -
Scaling: -
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Data type: FloatingPoint32
Data set: -
Data type: Unsigned16
Data set: -
0 signal
No
No
No
No
Data type: Unsigned16
Data set: -
Data type: Unsigned16
Data set: -
0 signal
No
No
No
No
No
No
No
© Siemens AG 2009 All Rights Reserved
FP
-
-
-
-
FP
-
-
-
-
-
-
-

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu230p-2 dpCu230p-2 can

Table of Contents