Example On How To Connect A Star Connected Three-Phase Ct Set To The Ied - ABB REG670 Applications Manual

Relion 670 series generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

1MRK 502 071-UEN -
4.2.2.5
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
However, in some cases, the following rated secondary currents are used as well:
2A
10A
The IED fully supports all of these rated secondary values.
It is recommended to:
use 1A rated CT input into the IED in order to connect CTs with
1A and 2A secondary rating
use 5A rated CT input into the IED in order to connect CTs with
5A and 10A secondary rating
Example on how to connect a star connected three-phase CT set to the
IED
Figure
18
gives an example about the wiring of a star connected two-phase CT set to
the IED. It gives an overview of the actions which are needed to make this
measurement available to the built-in protection and control functions within the IED
as well.
For correct terminal designations, see the connection diagrams valid
for the delivered IED.
Section 4
Analog inputs
71