Event Function Event - ABB REG670 Applications Manual

Relion 670 series generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

Section 17
Monitoring
17.5
17.5.1
17.5.2
17.5.3
642
RatedFltCurr: Rated fault current of the circuit breaker.
OperNoRated: Number of operations possible at rated current.
OperNoFault: Number of operations possible at rated fault current.
CBLifeAlmLevel: Alarm level for circuit breaker remaining life.
AccSelCal: Selection between the method of calculation of accumulated energy.
OperTimeDelay: Time delay between change of status of trip output and start of main
contact separation.

Event function EVENT

Identification
Function description
Event function
Application
When using a Substation Automation system with LON or SPA communication,
time-tagged events can be sent at change or cyclically from the IED to the station level.
These events are created from any available signal in the IED that is connected to the
Event function (EVENT). The EVENT function block is used for LON and SPA
communication.
Analog, integer and double indication values are also transferred through the EVENT
function.
Setting guidelines
The input parameters for the Event function (EVENT) can be set individually via the
local HMI (Main Menu/Settings / IED Settings / Monitoring / Event Function) or
via the Parameter Setting Tool (PST).
EventMask (Ch_1 - 16)
The inputs can be set individually as:
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
IEC 61850
IEC 60617
identification
identification
EVENT
S00946 V1 EN
1MRK 502 071-UEN -
ANSI/IEEE C37.2
device number
-
Application manual