ABB REG670 Applications Manual page 188

Relion 670 series generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

Section 7
Differential protection
182
level can be required. The setting is normally 1.0 but in multi-breaker arrangement the
setting shall be CT primary rating/IBase.
CTFactorPri2: A factor to allow a sensitive function also at multi-breaker
arrangement where the rating in the bay is much higher than the rated current of the
transformer winding. The stabilizing can then be high so an unnecessary high fault
level can be required. The setting is normally 1.0 but in multi-breaker arrangement the
setting shall be CT primary rating/IBase.
CTFactorSec1: See setting CTFactorPri1. Only difference is that CTFactorSec1 is
related to W2 side.
CTFactorSec2: See setting CTFactorPri2. Only difference is that CTFactorSec2 is
related to W2 side.
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
1MRK 502 071-UEN -
Application manual