Section 16
Logic
16.10.1
16.10.2
614

Identification

Function description
Integer to boolean 16 conversion
Application
Integer to boolean 16 conversion function (IB16) is used to transform an integer into
a set of 16 binary (logical) signals. It can be used – for example, to connect integer
output signals from one function to binary (logical) inputs to another function. IB16
function does not have a logical node mapping.
The Boolean 16 to integer conversion function (IB16) will transfer a combination of
up to 16 binary inputs INx where 1≤x≤16 to an integer. Each INx represents a value
according to the table below from 0 to 32768. This follows the general formula: INx
x-1
= 2
where 1≤x≤16. The sum of all the values on the activated INx will be available
on the output OUT as a sum of the values of all the inputs INx that are activated. OUT
is an integer. When all INx where 1≤x≤16 are activated that is = Boolean 1 it
corresponds to that integer 65535 is available on the output OUT. IB16 function is
designed for receiving up to 16 booleans input locally. If the BLOCK input is
activated, it will freeze the output at the last value.
Values of each of the different OUTx from function block IB16 for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the output
OUT on the function block IB16.
Name of input
Type
IN1
BOOLEAN
IN2
BOOLEAN
IN3
BOOLEAN
IN4
BOOLEAN
IN5
BOOLEAN
IN6
BOOLEAN
IN7
BOOLEAN
IN8
BOOLEAN
IN9
BOOLEAN
IN10
BOOLEAN
IN11
BOOLEAN
IN12
BOOLEAN
IN13
BOOLEAN
IN14
BOOLEAN
IN15
BOOLEAN
IN16
BOOLEAN
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
IEC 61850
IEC 60617
identification
identification
IB16
Default
Description
0
Input 1
0
Input 2
0
Input 3
0
Input 4
0
Input 5
0
Input 6
0
Input 7
0
Input 8
0
Input 9
0
Input 10
0
Input 11
0
Input 12
0
Input 13
0
Input 14
0
Input 15
0
Input 16
1MRK 502 071-UEN -
ANSI/IEEE C37.2
device number
-
-
Value when
Value when
activated
deactivated
1
0
2
0
4
0
8
0
16
0
32
0
64
0
128
0
256
0
512
0
1024
0
2048
0
4096
0
8192
0
16384
0
32768
0
Application manual