Section 6
Wide area measurement system
122
Each category has its corresponding parameter settings except for BINARYREPORT
function block which does not have any specific parameters and settings.
1.
PMUREPORT is the main function block which controls the operation of other
PMU reporting function blocks. Each instance of PMUREPORT function block
has the following parameters:
Operation: Enables/Disables the operation of the corresponding instance of
PMU reporting functionality by choosing On/Off setting.
SvcClass: It refers to the 1-byte SVC_CLASS field of the configuration
frame 3 (CFG-3) organization defined in IEEE C37.118.2 message format.
Here the user can select the performance class (service class) used for
synchrophasor data measurement according to IEEE C37.118.1 standard.
The options are P class or M class.
Note: There are 2 PMUREPORT instances available (PMUREPORT:1
and PMUREPORT:2) corresponding to 2 independent data streams. The
user can set different or identical service class for each data stream. In case
of different service classes, special rules shall be considered in PCM600
ACT for the connection of preprocessor blocks (SMAI) and 3PHSUM
blocks to PHASORREPORT blocks. More details are available under
section
PMU Report Function Blocks Connection Rules in PCM600
Application Configuration Tool
Global_PMU_ID: It refers to the 16-byte G_PMU_ID field of the
configuration frame 3 (CFG-3) organization defined in IEEE C37.118.2
message format. It is a 16-character (128 bits) user-assigned value which
can be sent with the configuration 3 message. It allows uniquely identifying
PMUs in a system that has more than 65535 PMUs. The coding for the 16
bytes is left to the user for assignment.
PMUdataStreamIDCODE: It refers to the 2-byte IDCODE field of the
configuration frame and data frame organization defined in IEEE
C37.118.2 message format. It is a user assigned ID number (1-65534) for
each data stream sent out from the PMU. This is especially important when
having multiple data streams (multiple PMU functionality).
Note: The data stream IDCODE is a unique code for each and every data
stream in one physical PMU device. In the IED, there are 2 PMUREPORT
instances available (PMUREPORT:1 and PMUREPORT:2)
corresponding to 2 independent data streams. The user must set different
IDCODEs for each instance.
PhasorFormat: It refers to the Bit 0 of the FORMAT field of the
configuration frames 1, 2 and 3 organization defined in IEEE C37.118.2
message format. Here the user can select the format of the calculated
synchrophasors. The options are Rectangular or Polar format. Rectangular
format represents the synchrophasor as real and imaginary values, real
value first (a + bj) while the Polar format represents the synchrophasor as
magnitude and angle, magnitude first (A e
PhasorDataType: It refers to the Bit 1 of the FORMAT field of the
configuration frames 1, 2 and 3 organization defined in IEEE C37.118.2
message format. Here the user can select the data type of the calculated
synchrophasors. The options are Integer or Float data. The synchrophasor
data are sent via the PHASORS field of data frame organization of IEEE
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
1MRK 502 071-UEN -
(ACT).
).
Application manual