Section 12
Multipurpose protection
12.1.2.1
446
Definite time delay or Inverse Time Overcurrent TOC/IDMT delay for
both steps
Second harmonic supervision is available in order to only allow operation
of the overcurrent stage(s) if the content of the second harmonic in the
measured current is lower than pre-set level
Directional supervision is available in order to only allow operation of the
overcurrent stage(s) if the fault location is in the pre-set direction (Forward
or Reverse). Its behavior during low-level polarizing voltage is settable
(Non-Directional,Block,Memory)
Voltage restrained/controlled feature is available in order to modify the
pick-up level of the overcurrent stage(s) in proportion to the magnitude of
the measured voltage
Current restrained feature is available in order to only allow operation of the
overcurrent stage(s) if the measured current quantity is bigger than the set
percentage of the current restrain quantity.
2.
Two undercurrent steps with the following built-in features:
Definite time delay for both steps
3.
Two overvoltage steps with the following built-in features
Definite time delay or Inverse Time Overcurrent TOC/IDMT delay for
both steps
4.
Two undervoltage steps with the following built-in features
Definite time delay or Inverse Time Overcurrent TOC/IDMT delay for
both steps
All these four protection elements within one general protection function works
independently from each other and they can be individually enabled or disabled.
However it shall be once more noted that all these four protection elements measure
one selected current quantity and one selected voltage quantity (see table
table 49). It is possible to simultaneously use all four-protection elements and their
individual stages. Sometimes in order to obtain desired application functionality it is
necessary to provide interaction between two or more protection elements/stages
within one CVGAPC function by appropriate IED configuration (for example, dead
machine protection for generators).

Current and voltage selection for CVGAPC function

CVGAPC function is always connected to three-phase current and three-phase
voltage input in the configuration tool, but it will always measure only the single
current and the single voltage quantity selected by the end user in the setting tool
(selected current quantity and selected voltage quantity).
The user can select, by a setting parameter CurrentInput, to measure one of the
following current quantities shown in table 48.
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
1MRK 502 071-UEN -
48
and
Application manual