Negative sequence overcurrent protection

Example will be given how to use one CVGAPC function to provide negative
sequence inverse time overcurrent protection for a generator with capability constant
of 20s, and maximum continuous negative sequence rating of 7% of the generator
rated current.
The capability curve for a generator negative sequence overcurrent protection, often
used world-wide, is defined by the ANSI standard in accordance with the following
formula:
k
=
t
op
2
æ
ö
I
NS
ç
÷
I
è
ø
r
EQUATION1372 V1 EN
where:
t
is the operating time in seconds of the negative sequence overcurrent IED
op
k
is the generator capability constant in seconds
I
is the measured negative sequence current
NS
I
is the generator rated current
r
By defining parameter x equal to maximum continuous negative sequence rating of
the generator in accordance with the following formula
=
=
x
7%
0, 07
pu
EQUATION1373 V1 EN
Equation
249
can be re-written in the following way without changing the value for
the operate time of the negative sequence inverse overcurrent IED:
1
×
k
2
x
=
t
op
2
æ
ö
I
NS
ç
÷
×
x I
è
ø
r
EQUATION1374 V1 EN
In order to achieve such protection functionality with one CVGAPC functions the
following must be done:
Section 12
Multipurpose protection
(Equation 249)
(Equation 250)
(Equation 251)
453