Example 1; Example 2 - ABB REG670 Applications Manual

Relion 670 series generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

1MRK 502 071-UEN -
4.2.2.1
4.2.2.2
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual

Example 1

Two IEDs used for protection of two objects.
Transformer
I
p
Transformer
I
s
protection
IED
Setting of current input:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
IEC05000753 V2 EN
Figure 12:
Example how to set CTStarPoint parameters in the IED
Figure
12
shows the normal case where the objects have their own CTs. The settings
for CT direction shall be done according to the figure. To protect the line, direction of
the directional functions of the line protection shall be set to Forward. This means that
the protection is looking towards the line.

Example 2

Two IEDs used for protection of two objects and sharing a CT.
I
I
p
p
I
s
Setting of current input:
Setting of current input:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Section 4
Analog inputs
Line
Line
Reverse
Forward
Definition of direction
for directional functions
Line protection
IED
Set parameter
CTStarPoint with
Line as
reference object.
Correct setting is
"FromObject"
IEC05000753=IEC05
000753=1=en=Origin
al[1].vsd
65