A safety margin of 5% for the maximum static inaccuracy and a safety margin of 5%
for maximum possible transient overreach have to be introduced. An additional 20%
is suggested due to inaccuracy of instrument transformers under transient conditions
and inaccuracy in the system data.
The minimum primary current setting (Is) is:
I
= 1.3 × I
s
min
EQUATION285 V3 EN
In case of parallel lines with zero sequence mutual coupling a fault on the parallel line,
as shown in Figure 179, should be calculated.
A
Z
~
A
Fault
IED
IEC09000025 V1 EN
Figure 179:
Two parallel lines. Influence from parallel line to the through fault
current: I
The minimum theoretical current setting (Imin) will in this case be:
³
,
,
I m in
M A X I
(
I
I
)
fA
fB
M
EQUATION287 V1 EN
Where:
I
and I
have been described for the single line case.
fA
fB
Considering the safety margins mentioned previously, the minimum setting (Is) is:
I
= 1.3 × I
s
min
EQUATION288 V3 EN
The IED setting value IN>> is given in percent of the primary base current value,
IBase. The value for IN>> is given by the formula:
Line 1
C
B
Z
L1
M
Z
L2
I
M
Line 2
M
Section 9
Current protection
(Equation 188)
Z
~
B
IEC09000025-1-en.vsd
(Equation 189)
(Equation 190)
337